Tripp Lite 9PX6KL Eaton 9PX 6KVA Lithium-Ion Advanced Users Guide 9PX6K-L 9PXE - Page 47
AllModels, NormalMode, Battery Mode, Model, OutputConnection, Output Cable, Table14.
View all Tripp Lite 9PX6KL manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 47 highlights
Model Specifications Table 12. Electrical Output (Continued) All Models Normal Mode Battery Mode Output short-circuit current Max RMS & delay time: 56.5A/150ms; The max peak value: 92A * 200/208/220/230V are derated at 4600/4800/5100/5300. Table 13. Electrical Output Connections Model Output Connection 9PX6K-L Hardwired (2) L6-30R (2) L6-20R Output Cable No Table 14. Environmental and Safety Certifications EMC ( Emissions)* EMC (Immunity) * for output cable < 10m. Agency Markings Operating Temperatures Storage Temperatures Transit Temperature Relative Humidity Operating Altitude EN/IEC 62040-1 EN/IEC 62040-2 EN/IEC 62040-3 UL1778 5th edition CSA 22.2 CISPR32 (EN55032) Class A AS/NZS CISPR32 Class A IEC 61000 -3-11 IEC 61000 -3-12 FCC part 15 Class A IEC 61000-2-2 IEC 61000-4-2, Level 3 IEC 61000-4-3, Level 3 IEC 61000-4-4, Level 4 (also on signal ports) IEC 61000-4-5, Level 4, Criteria B IEC 61000-4-6, Level 3 IEC 61000-4-8, Level 4 IEC 61000-4-12 CE cULus ; UKCA; RCM; Ukr; EAC; Cmim 0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude Note: thermal protection switches load to Bypass in case of overheating. 0 to 40°C (32 to 104°F) with batteries -15 to 60°C (5 to 140°F) without batteries -25 to 55°C (-13 to 130°F) 0 to 95% no condensing Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m Eaton 9PX Lithium-Ion User Guide DPD-9PX2206-Rev 01 41