Tripp Lite 9PX6KL Eaton 9PX 6KVA Lithium-Ion Advanced Users Guide 9PX6K-L 9PXE - Page 34

Setting High Efficiency Mode, Configuring Bypass Settings, Configuring Battery Settings, Retrieving

Page 34 highlights

Setting High Efficiency Mode 6.6 Setting High Efficiency Mode In High Efficiency mode, the UPS operates normally on Bypass and transfers to Online (or Battery) mode in less than 10 ms when utility fails. Transfers to High Efficiency mode will be active after 5 minutes of Bypass voltage monitoring: if Bypass quality is not in tolerance, then the UPS will remain in Online mode. Eaton recommends to use the HE mode only to protect IT equipment. To set the High Efficiency mode: 1. Select Settings, In/Out settings, and High Efficiency mode. 2. Select Enabled and Enter to confirm. 3. The UPS transfers to High Efficiency mode after 5 minutes. 6.7 Configuring Bypass Settings The following settings are available for configuring Bypass operation. Bypass Transfer out of tolerance 1. Press any button to activate the menu options, then select Settings, Output settings, and Bypass transfer. 2. Select Enabled or Disabled for BP AC NOK, and Enter to confirm. If Enabled, the UPS transfers to Bypass even if Bypass AC source is out of tolerance, depending on output mode. If Disabled, the UPS output is shutdown. 6.8 Configuring Battery Settings Low battery warning During discharge, the low battery alarm is activated if the battery capacity goes below 20%. This threshold can be modified. 6.9 Retrieving the Event Log To retrieve the Event log through the display: 1. Press any button to activate the menu options, then select Event log. 2. Scroll through the listed events. 6.10 Retrieving the Fault Log To retrieve the Fault log through the display: 1. Press any button to activate the menu options, then select Fault log. 2. Scroll through the listed faults. 28 Eaton 9PX Lithium-Ion User Guide DPD-9PX2206-Rev 01

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50

28
Eaton 9PX Lithium-Ion User Guide DPD-9PX2206—Rev 01
6.6
Setting High Efficiency Mode
InHighEfficiencymode,theUPSoperatesnormallyonBypassandtransferstoOnline(orBattery)modeinless
than10mswhenutilityfails.TransferstoHighEfficiencymodewillbeactiveafter5minutesofBypassvoltage
monitoring:ifBypassqualityisnotintolerance,thentheUPSwillremaininOnlinemode.
EatonrecommendstousetheHEmodeonlytoprotectITequipment.
TosettheHighEfficiencymode:
1. Select Settings, In/Out settings, and High Efficiency mode.
2. Select Enabled and Enter to confirm.
3. The UPS transfers to High Efficiency mode after 5 minutes.
6.7
Configuring Bypass Settings
ThefollowingsettingsareavailableforconfiguringBypassoperation.
BypassTransferoutoftolerance
1. Press any button to activate the menu options, then select Settings, Output settings, and Bypass transfer.
2. Select Enabled or Disabled for BP AC NOK, and Enter to confirm. If Enabled, the UPS transfers to Bypass
evenifBypassACsourceisoutoftolerance,dependingonoutputmode.IfDisabled,theUPSoutputis
shutdown.
6.8
Configuring Battery Settings
Lowbatterywarning
Duringdischarge,thelowbatteryalarmisactivatedifthebatterycapacitygoesbelow20%.Thisthresholdcan
bemodified.
6.9
Retrieving the Event Log
To retrieve the Event log through the display:
1. Press any button to activate the menu options, then select Event log.
2. Scroll through the listed events.
6.10 Retrieving the Fault Log
ToretrievetheFaultlogthroughthedisplay:
1. Press any button to activate the menu options, then select Fault log.
2. Scroll through the listed faults.
SettingHighEfficiencyMode