Tripp Lite 9PXEBM180RT Eaton 9PX3K3U and 9PX EBM 180 V Installation and User M - Page 23

Installation requirements

Page 23 highlights

ENGLISH 3. Installation 3.9 Installation requirements Recommended protective devices and cable cross-sections 1. Recommended upstream protection UPS power rating 9PX3K3U Upstream circuit breaker D curve - 30A 2 poles circuit breaker L1 N(L2) to UPS Normal AC source G N(L2) L1 2. Recommended cable cross-sections Terminal position L1 N(L2) Wire function Phase Neutral (Phase) Ground Terminal wire size rating 4-16 mm2 (12-6 AWG) Copper wire, solid or stranted. Minimum input wire size 6 mm2 (10 AWG) 105°C Tightening torque 10 lb in / 1.13 Nm 10 mm2 (8 AWG) 75°C 9PX3K3U_EN Page 23

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46

Page 23
9PX3K3U_EN
ENGLISH
3.9
Installation requirements
Recommended protective devices and cable cross-sections
1.
Recommended upstream protection
UPS power rating
Upstream circuit breaker
9PX3K3U
D curve – 30A
2 poles circuit breaker
G N(L2) L1
N(L2)
L1
to UPS Normal AC source
2.
Recommended cable cross-sections
Terminal
position
Wire
function
Terminal wire
size rating
Minimum input
wire size
Tightening
torque
L1
Phase
4-16 mm
2
(12-6 AWG)
6 mm
2
(10 AWG) 105°C
10 mm
2
(8 AWG) 75°C
10 lb in / 1.13 Nm
N(L2)
Neutral
(Phase)
Ground
Copper wire, solid or stranted.
3. Installation