Tripp Lite 9PXEBM180RT Eaton 9PX3K3U and 9PX EBM 180 V Installation and User M - Page 23
Installation requirements
![]() |
View all Tripp Lite 9PXEBM180RT manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 23 highlights
ENGLISH 3. Installation 3.9 Installation requirements Recommended protective devices and cable cross-sections 1. Recommended upstream protection UPS power rating 9PX3K3U Upstream circuit breaker D curve - 30A 2 poles circuit breaker L1 N(L2) to UPS Normal AC source G N(L2) L1 2. Recommended cable cross-sections Terminal position L1 N(L2) Wire function Phase Neutral (Phase) Ground Terminal wire size rating 4-16 mm2 (12-6 AWG) Copper wire, solid or stranted. Minimum input wire size 6 mm2 (10 AWG) 105°C Tightening torque 10 lb in / 1.13 Nm 10 mm2 (8 AWG) 75°C 9PX3K3U_EN Page 23
![](/manual_guide/products/tripp-lite-9px3k3unp1-eaton-9px3k3u-9px-ebm-180-v-installation-user-manual-1b07656/23.png)
Page 23
9PX3K3U_EN
ENGLISH
3.9
Installation requirements
Recommended protective devices and cable cross-sections
1.
Recommended upstream protection
UPS power rating
Upstream circuit breaker
9PX3K3U
D curve – 30A
2 poles circuit breaker
G N(L2) L1
N(L2)
L1
to UPS Normal AC source
2.
Recommended cable cross-sections
Terminal
position
Wire
function
Terminal wire
size rating
Minimum input
wire size
Tightening
torque
L1
Phase
4-16 mm
2
(12-6 AWG)
6 mm
2
(10 AWG) 105°C
10 mm
2
(8 AWG) 75°C
10 lb in / 1.13 Nm
N(L2)
Neutral
(Phase)
Ground
Copper wire, solid or stranted.
3. Installation