Tripp Lite 9PXEBM180RT Eaton 9PX3K3U and 9PX EBM 180 V Installation and User M - Page 43
Remote On/Off
View all Tripp Lite 9PXEBM180RT manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 43 highlights
ENGLISH 9. Specifications Agency markings Operating temperature Storage temperature Transit temperature Relative humidity Operating altitude Transit altitude Audible noise CE / cULus / energy star 0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude Note: thermal protection switches load to Bypass in case of overheating. 0 to 40°C (32 to 104°F) with batteries -15 to 60°C (5 to 140°F) without batteries -25 to 55°C (-13 to 130°F) 0 to 95% no condensing Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m Up to 10,000 meters (32,808 ft) above sea level < 45 dBA at 1 meter typical Table 9. Battery Rack / Tower configuration Type Monitoring Battery port EBM battery cable length Internal batteries 9PX3K3U: 180Vdc EBM 9PXEBM180RT: 180Vdc Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float service life at 25°C (77°F). Lifetime is reduced above 30°C. Advanced monitoring for earlier failure detection and warning External three-pole SBS75G Black connector on UPS for connection to EBM 40cm (15.7in) Table 10. Communication options Communication bay Compatible connectivity cards Communication ports Relay output contacts Remote On/Off Remote Power Off (1) available independent communication bay for connectivity cards Network-MS Modbus-MS Relay-MS RS-232 (DB9): 1200-19200 bps USB: 19200 bps (4) relay outputs (normally open or normally closed) 2 pins jumper (normally open) 3 pins jumper (normally open or normally closed) 9PX3K3U_EN Page 43