Tripp Lite 9PXEBM180RT Eaton 9PX3K3U and 9PX EBM 180 V Installation and User M - Page 37

Replacing the UPS equipped with a HotSwap MBP or with a PPDM, Recycling the used equipment

Page 37 highlights

ENGLISH 7. UPS maintenance 7.5 Replacing the UPS equipped with a HotSwap MBP or with a PPDM The HotSwap MBP as well as the PPDM allows to service or replace the UPS without interrupting the connected loads. Refer to the specific user manual for more information about this accessory. • Replacing the UPS equipped with a HotSwap MBP. To remove the UPS: 1. Press any button to activate the menu options. Select Control then Go to Bypass. 2. Check that the UPS is in Bypass mode (Bypass LED should be On). 3. Turn the HotSwap MBP switch to the Bypass position: the red LED on the HotSwap MBP goes On, indicating that the load is now powered directly from utility power. 4. Set the Normal AC source switch on the HotSwap MBP to the "O" position and wait for 30s. 5. The UPS stops and can now be disconnected. To reinstall the UPS: 1. Check that the UPS is correctly connected to the HotSwap MBP. 2. Set the Normal AC source switch on the HotSwap MBP to the "I" position. 3. Press the button to switch On the UPS. 4. Select Control then Go to Bypass (Bypass LED should be On). 5. Turn the HotSwap MBP switch to the Normal position: the red LED on the HotSwap MBP goes Off, indicating that the load is now powered by the UPS. 6. Select Control then Go back normal. 7. Check that the UPS is in Online mode: the load is now protected by the UPS. (Online LED should be On). • Replacing the UPS equipped with a PPDM. To remove the UPS: 1. Press any button to activate the menu options. Select Control then Go to Bypass. 2. Check that the UPS is in Bypass mode (Bypass LED should be On). 3. Remove the center cover of the PPDM front panel. 4. Turn the PPDM switch to the Bypass position: the load is now powered directly from utility power. 5. Press the button to switch Off the UPS. 6. The UPS is in Standby mode and can now be disconnected. To reinstall the UPS: 1. Check that the UPS is correctly connected to the PPDM. 2. Press the button to switch On the UPS. 3. Select Control then Go to Bypass. 4. Check that the UPS is in Bypass mode (Bypass LED should be On). 5. Turn the PPDM switch to the Normal position: the load is now powered by the UPS. 6. Clip back the center cover of the PPDM front panel. 7. Select Control then Go back normal. 8. Check that the UPS is in Online mode: the load is now protected by the UPS. 7.6 Recycling the used equipment Contact your local recycling or hazardous waste center for information on proper disposal of the used equipment. • Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. • Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid batteries and must be disposed of properly. For more information, contact your local recycling/ reuse or hazardous waste center. Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 9PX3K3U_EN Page 37

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46

Page 37
9PX3K3U_EN
ENGLISH
7. UPS maintenance
7.5
Replacing the UPS equipped with a HotSwap MBP or with a PPDM
The HotSwap MBP as well as the PPDM allows to service or replace the UPS without interrupting the
connected loads.
Refer to the specific user manual for more information about this accessory.
Replacing the UPS equipped with a HotSwap MBP.
To remove the UPS:
1.
Press any button to activate the menu options. Select Control then Go to Bypass.
2.
Check that the UPS is in Bypass mode (Bypass LED should be On).
3.
Turn the HotSwap MBP switch to the Bypass position: the red LED on the HotSwap MBP goes On,
indicating that the load is now powered directly from utility power.
4.
Set the Normal AC source switch on the HotSwap MBP to the "O" position and wait for 30s.
5.
The UPS stops and can now be disconnected.
To reinstall the UPS:
1.
Check that the UPS is correctly connected to the HotSwap MBP.
2.
Set the Normal AC source switch on the HotSwap MBP to the "I" position.
3.
Press the
button to switch On the UPS.
4.
Select Control then Go to Bypass (Bypass LED should be On).
5.
Turn the HotSwap MBP switch to the Normal position: the red LED on the HotSwap MBP goes Off,
indicating that the load is now powered by the UPS.
6.
Select Control then Go back normal.
7.
Check that the UPS is in Online mode: the load is now protected by the UPS. (Online LED should be On).
Replacing the UPS equipped with a PPDM.
To remove the UPS:
1.
Press any button to activate the menu options. Select Control then Go to Bypass.
2.
Check that the UPS is in Bypass mode (Bypass LED should be On).
3.
Remove the center cover of the PPDM front panel.
4.
Turn the PPDM switch to the Bypass position: the load is now powered directly from utility power.
5.
Press the
button to switch Off the UPS.
6.
The UPS is in Standby mode and can now be disconnected.
To reinstall the UPS:
1.
Check that the UPS is correctly connected to the PPDM.
2.
Press the
button to switch On the UPS.
3.
Select Control then Go to Bypass.
4.
Check that the UPS is in Bypass mode (Bypass LED should be On).
5.
Turn the PPDM switch to the Normal position: the load is now powered by the UPS.
6.
Clip back the center cover of the PPDM front panel.
7.
Select Control then Go back normal.
8.
Check that the UPS is in Online mode: the load is now protected by the UPS.
7.6
Recycling the used equipment
Contact your local recycling or hazardous waste center for information on proper disposal of the used
equipment.
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of
batteries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid
batteries and must be disposed of properly. For more information, contact your local recycling/
reuse or hazardous waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper
disposal, contact your local recycling/reuse or hazardous waste center.