Tripp Lite SU5000RT4UHV Owner's Manual for SmartOnline Single-Phase 5kVA-6kVA - Page 20
Start Settings, Charger Settings
View all Tripp Lite SU5000RT4UHV manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 20 highlights
Operation (continued) Start Settings The UPS can start up through the battery without AC power. The DEFAULT is ENABLE. When the UPS switches to battery it can AUTO RESTART to work in an On-Line Mode when AC power is restored. DEFAULT is ENABLE. From the SETUP MENU screen, scroll DOWNi to the START SETTING screen. From here, press the ON button for the BATTERY START screen. From this screen, pressing ON moves you to a ENABLE screen. Pressing ON will ENABLE, while scrolling DOWNi takes you to a DISABLE screen. From here, press ON to DISABLE this function. From the BATTERY START screen, pressing DOWNi will take you to an AUTO RESTART screen. Pressing ON takes you to an ENABLE screen; press ON to ENABLE. Pressing DOWNi takes you to a DISABLE screen. Press ON to DISABLE this function. START SETTING ENT DOWN UP BATTERY START ENT DOWN UP *ENABLE* ENT DOWN UP To ENTER DISABLE ENT DOWN UP AUTO RESTART ENT DOWN UP *ENABLE* ENT DOWN UP DISABLE ENT DOWN UP Charger Settings From the SETUP MENU screen, scroll DOWNi until you reach the CHARGER SETTING screen. From here, press ON to get to the CHARGER CURRENT screen. Press ON again. From here, you can scroll DOWNi or UPh to select current values between 0.7 and 4.0 A. Press ON to save your desired value. The DEFAULT selection is 0.7A. CHARGER SETTING ENT DOWN UP CHARGER CURRENT ENT DOWN UP CURRENT = 0.7A ENT DOWN UP To ENTER CURRENT = 1.5A ENT DOWN UP CURRENT = 3.0A ENT DOWN UP CURRENT = 4.0A* ENT DOWN UP Use the following table as a guide for charger settings based on the number of battery packs you are using. UPS Charge Current Setting for 5/6kVA Models Internal Battery Pack + External Battery Packs 1 2 Charge Current Setting 0.7A 1.5A 3-6 3.0A 7 or more 4.0A UPS Charge Current Settings for the 12kVA Model Use the same charger current settings as the 5/6kVA models for each power module of the SU12KRT4UHW. The number of connected external battery packs must be equal on each power module of the SU12KRT4UHW. 20 201207113 933070.indb 20 9/17/2012 1:20:08 PM