Tripp Lite SU5000RT4UHV Owner's Manual for SmartOnline Single-Phase 5kVA-6kVA - Page 26

UPS Fault Shutdown Messages, On Battery Alarm, Overload Messages, Bypass Messages

Page 26 highlights

Operation (continued) UPS Fault Shutdown Messages CONDITION LCD DISPLAY MESSAGES +BUS >450V + DC BUS HIGH SHUTDOWN Load 100%: +BUS 450V - DC BUS HIGH SHUTDOWN Load 15% Higher Than Nominal BYPS OUT OF VOLT XXXV / XX.X HZ >20% Lower Than Nominal BYPS OUT OF VOLT XXXV / XX.X HZ 26 201207113 933070.indb 26 9/17/2012 1:20:08 PM

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116

26
UPS Fault Shutdown Messages
CONDITION
LCD DISPLAY MESSAGES
+BUS >450V
+ DC BUS HIGH
SHUTDOWN
Load <100%: +BUS < 320V; Load >100%: +BUS
<290V
+ DC BUS LOW
SHUTDOWN
-BUS >450V
- DC BUS HIGH
SHUTDOWN
Load <100%: -BUS <320V; Load >100%: -BUS <290V
- DC BUS LOW
SHUTDOWN
BUS Voltage Over 500
BUS OVP FAIL
SHUTDOWN
Output Short
OUTPUT SHORT
SHUTDOWN
UPS Over Temperature
OVER TEMPERATURE
SHUTDOWN
Ouput SCR Open Failure
OUTPUT SCR FAIL
SHUTDOWN
Output Overload
OVERLOAD
SHUTDOWN
Bypass SCR Short
BYPASS SCR FAIL
SHUTDOWN
Input SCR Rectifier Failure
RECTIFIER FAIL
SHUTDOWN
Inverter Output Voltage Failure
INVERTER
SHUTDOWN
Input Fuse Open
I / P FUSE BROKEN
SHUTDOWN
Output Fuse Open
O / P FUSE BROKEN
SHUTDOWN
Parallel ID Lost
PARALLEL FAULT
SHUTDOWN
On Battery Alarm
When in the On Battery Mode, the UPS power module will beep to inform you that it is using battery power to support
connected equipment. If its connected batteries are at more than half capacity, it will beep every two seconds. If its
connected batteries are below half capacity, it will beep twice a second. If its connected batteries are nearly depleted, the
UPS power module will beep continuously.
To silence the On Battery Alarm, press the “ON/MUTE” button.
Overload Messages
When the UPS detects an output overload, its LCD will switch to the following display:
The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to
Bypass Mode to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:
Overload Condition
Countdown Duration
106% - 125%
1 minute
126% - 150%
30 seconds
>150%
Immediate
Bypass Messages
While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS
will not provide battery backup in Bypass Mode.
If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS
displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level,
the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time,
but has returned to nominal.
>15% Higher
Than Nominal
>20% Lower
Than Nominal
BYPASS VOLTAGE
CONDITIONS
LCD DISPLAY
MESSAGES
BYPS OUT OF VOLT
XXXV / XX.X HZ
BYPS OUT OF VOLT
XXXV / XX.X HZ
Operation
(continued)
OVERLOAD!
LOAD = XXX% X.XXKW
201207113 933070.indb
26
9/17/2012
1:20:08 PM