Viking VGR548 Installation Instructions - Page 11

Wood/Composite Overlay

Page 11 highlights

Clearance Dimensions (Wood/Composite Overlay) The bottom of a standard hood should be 30" (76.2 cm) min. to 36" (91.4 cm) max. above the countertop. This would typically result in the bottom of the hood being 66" (167.6 cm) to 72" (182.9 cm) above the floor. Refer to the range hood installation instructions for additional information. These dimensions provide for safe and efficient operation of the hood. WoodO/Cveormlapyosite ((7611268672""t..mmo69 accinmmx..)) WoodO/Cveormlapyosite (612.04"cm) (00c"m) 33((796061""..t24mmoccaimmnx.)). ((7611268672""t..mmo69 accinmmx..)) Island Installation (763.20"cm) (156.2"cm) 33((796061""..t24mmoccaimmnx.)). Wall Installation Note: Minimum clearance for back wall is 0" with backguard or highshelf. Note: This range comes standard with an Island Trim. There must be a minimum of 6" (15.2 cm) clearance from rear of range to a combustible wall or 0" clearance to a non-combustible wall. Note: Clearances from non-combustible materials are not part of the ANSI Z21.1 scope and not certified by CSA. Clearances to non-combustible materials must be approved by the authority having jurisdiction. 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24

11
The bottom of a standard hood should be
30” (76.2 cm) min. to 36” (91.4 cm) max.
above the countertop. This would
typically result in the bottom of the hood
being 66” (167.6 cm) to 72” (182.9 cm)
above the floor. Refer to the range hood
installation instructions for additional
information. These dimensions provide for
safe and efficient operation of the hood.
66
min.
(167.6 cm)
to
72
max.
(182.9 cm)
30
(76.2 cm)
6
(15.2 cm)
Wood/Composite
Overlay
30
min.
(76.2 cm)
to
36
max.
(91.4 cm)
66
min.
(167.6 cm)
to
72
max.
(182.9 cm)
24
(61.0 cm)
Wood/Composite
Overlay
0
(
0 cm)
30
min.
(76.2 cm)
to
36
max.
(91.4 cm)
Wall Installation
Island Installation
Note:
This range comes standard with an
Island Trim. There must be a minimum of
6” (15.2 cm) clearance from rear of range
to a
combustible
wall or 0” clearance to
a
non-combustible
wall.
Note:
Clearances from non-combustible
materials are not part of the ANSI Z21.1
scope and not certified by CSA.
Clearances to non-combustible materials
must be approved by the authority
having jurisdiction.
Note:
Minimum clearance for back
wall is 0” with backguard or high-
shelf.
Clearance Dimensions
(Wood/Composite Overlay)