Fisher and Paykel RDV3-304-N Installation Guide - Page 15

Electrical connection

Page 15 highlights

ELECTRICAL CONNECTION All models IMPORTANT! z This range must be connected to the mains power supply only by a suitably qualified person. z This range must be earthed. z Always disconnect electric supply cord from the wall outlet or service disconnect before servicing this appliance. z Observe all governing codes and ordinances when grounding, in absence of which, observe National Electrical Code ANSI / NFPA No. 70. The rating label is located under the control panel Wiring diagrams are also in the service summary, attached to the inside of the toe kick panel A wiring diagram label is attached to the back of the range RDV3 models z A neutral supply wire must be provided from the power source (breaker panel) because critical range components, including the surface burner spark reignition module, require 120/240 VAC to operate safely and properly. z If the correct power supply circuit is not provided, it is the responsibility and obligation of the installer and user to have proper power supply connected. This must be accomplished in accordance with all applicable local codes and ordinances by a qualified electrician. It is the responsibility of the installer to ensure compliance of local codes. In the absence of local codes and ordinances, the power supply connection shall be in accordance with the National Electric Code. z Observe all governing codes and ordinances when grounding. In the absence of these codes or ordinances observe National Electrical Code ANSI/NFPA No. 70 current issue. See the following information in this section for grounding method.. z Range connection: P1-P2: 240V or 208V; P1-N: 120V; P2-N: 120V; 60Hz; Ground/ Earth required. IMPORTANT! z An improper 120/240 VAC power supply will cause malfunction, damage to this appliance, and possibly create a condition of shock hazard. z Improper connection of aluminium house wiring can result in a fire or shock hazard. Use only connectors designed and certified for connecting to aluminium wire. MODEL RDV3-304 RIV3-304 RDV3-366 RIV3-365 RDV3-488 RDV3-485GD RDV3-486GD RHV3-484 MAX. CURRENT DRAW 27 A 57 A 29 A 72 A 44 A 44 A 44 A 75 A CIRCUIT* FREQUENCY 30 A 50 A 30 A 50 A 50 A 50 A 50 A 50 A 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz *NEC Calculated Circuit Load, this is less than the total connected load listed on the rating label. IMPORTANT! The fourth prong (round grounding pin) should not, under any circumstances, be cut or removed. 15

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22

15
All models
IMPORTANT!
z
This range must be connected to the mains power supply only by a suitably
qualified person.
z
This range must be earthed.
z
Always disconnect electric supply cord from the wall outlet or service disconnect
before servicing this appliance.
z
Observe all governing codes and ordinances when grounding, in absence of which,
observe National Electrical Code ANSI / NFPA No. 70.
RDV3 models
z
A neutral supply wire must be provided from the power source (breaker panel)
because critical range components, including the surface burner spark reignition module,
require 120/240 VAC to operate safely and properly.
z
If the correct power supply circuit is not provided, it is the responsibility and
obligation of the installer and user to have proper power supply connected.
This must be accomplished in accordance with all applicable local codes and ordinances
by a qualified electrician. It is the responsibility of the installer to ensure compliance
of local codes. In the absence of local codes and ordinances, the power supply
connection shall be in accordance with the National Electric Code.
z
Observe all governing codes and ordinances when grounding. In the absence of these
codes or ordinances observe National Electrical Code ANSI/NFPA No. 70 current issue.
See the following information in this section for grounding method..
z
Range connection: P1-P2: 240V or 208V;  P1-N: 120V;  P2-N: 120V;  60Hz;  Ground/
Earth required.
IMPORTANT!
z
An improper 120/240 VAC power supply will cause malfunction, damage to this
appliance, and possibly create a condition of shock hazard.
z
Improper connection of aluminium house wiring can result in a fire or shock hazard.
Use only connectors designed and certified for connecting to aluminium wire.
MODEL
MAX.
CURRENT DRAW
CIRCUIT*
FREQUENCY
RDV3-304
27 A
±0 A
60 Hz
RIV3-304
57 A
50 A
60 Hz
RDV3-366
29 A
±0 A
60 Hz
RIV3-365
72 A
50 A
60 Hz
RDV3-488
44 A
50 A
60 Hz
RDV3-485GD
44 A
50 A
60 Hz
RDV3-486GD
44 A
50 A
60 Hz
RHV3-484
75 A
50 A
60 Hz
*NEC Calculated Circuit Load, this is less than the total connected load listed on the rating label.
IMPORTANT!
The fourth prong (round grounding pin) should not, under any circumstances,
be cut or removed.
ELECTRICAL CONNECTION
Wiring diagrams are
also in the service
summary, attached
to the inside of the
toe kick panel
The rating label is
located under the
control panel
A wiring
diagram label
is attached to
the back of
the range