HP 2120 HP StorageWorks Disk System 2120 Users Guide (5697-5367, March 2005) - Page 11

Power Connector, Electrical Requirements, AC Site Requirements - disk

Page 11 highlights

Power Connector FIGURE 6 AC Power Connector Location HP StorageWorks Disk System 2120 11 English AC Power Connector Electrical Requirements AC Site Requirements Overcurrent protection devices are required for each cabinet where the disk system is installed. They must be positioned between the power source and the disk system. These protective devices must not trip when exposed to an inrush current of 30 amps lasting 5 ms. Note These protection devices must meet all applicable electrical safety requirements and be approved for the intended purpose. I TABLE 3 AC Power Requirements Electrical Element Requirements Voltage 100-240 VAC Frequency 50-60 Hz Input Current 1.7-0.7 amp* Maximum Surge Current 30 amps peak * Depending on voltage. Confirm through measurement.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38

11
HP
StorageWorks Disk System 2120
English
Power Connector
FIGURE 6
AC Power Connector Location
Electrical Requirements
AC Site Requirements
Overcurrent protection devices are required for each cabinet where the disk system is
installed. They must be positioned between the power source and the disk system.
These protective devices must not trip when exposed to an inrush current of 30 amps
lasting 5 ms.
I
Note
These protection devices must meet all applicable electrical safety
requirements and be approved for the intended purpose.
TABLE 3
AC Power Requirements
Electrical Element
Requirements
Voltage
100-240 VAC
Frequency
50-60 Hz
Input Current
1.7-0.7 amp
*
Maximum Surge Current
30 amps peak
*
Depending on voltage. Confirm through measurement.
AC
Power
Connector