INTRODUCTION ACCOUNT SETUP POWER NETWORK/MOUNTING ACCESS CONTROL Wire Specifications Use this chart to pull wires in preparation of your installation. Check the national and local building codes BEFORE installation. INTRODUCTION ACCOUNT SETUP POWER NETWORK/MOUNTING ACCESS CONTROL DESCRIPTION OF WIRE RUN WIRE SPECIFICATION MAXIMUM RUN DISTANCE Power Wire, secondary DC output 2-Conductor 14 AWG Up to 300 feet (91.4 m) 2-Conductor 16 AWG Up to 200 feet (60.9 m) 2-Conductor 18 AWG Up to 100 feet (30.4 m) Local Area Network (LAN) CINATT5ReOoDr bUeCtteTrINOeNtwork CabAle.CCOUNT SETUP 8-Conductor, 24 AWG Twisted pair 328 feet* (100 m) POWER NETWORK/MOUNTING ACCESS CONTROL Door Strike 2-Conductor 18-22 AWG Shielded 100 - 250 feet (30.5 - 76.2 m) Magnetic Lock 2-Conductor 18-22 AWG 50 - 125 feet (15.2 - 38.1 m) Dry Contact Closure (Most Gate Operators) 2-Conductor 18-24 AWG Shielded 500 - 2500 feet (152.4 - 762 m) Exit Request (REX) 2-Conductor 18-24 AWG 500 feet (152.4 m) SINupTeRrvOiseDdUInCpTuIt ON ACCOUNT SETUP Wiegand/Proximity Readers PO2W-CEoRnductoNr 1E8T-2W4OAWRKG /MOUNTING 50A0 CfeCetE(1S5S2.4CmO)NTROL 3-Conductor 18-22 AWG Shielded 500 feet (152.4 m) NOTE: Main power supply and control wiring MUST be run in separate conduits. Conduits must be UL approved for low and high voltage. Refer to the NEC for additional wiring requirements. Category 5e cabling is the minimum performance category recommended. WIiNrinTgRsOhaDllUbCe iTnIaOccNordance wAitChCthOe UNaNtiTonSalEETleUctPrical CodeP(OANWSEI/RNFPA 70N)E, lTocWalOcoRdKes/ManOdUauNthToIrNitiGes havAinCgCjuEriSsdSicCtioOnN. TROL Always provide power from a dedicated source. Plug provided transformer into an outlet wired to its own 10 Amp minimum circuit breaker. This will prevent two problems: • Other equipment cannot introduce spikes, noise, surges or dips into the power circuit that will affect the system. • The system's operation will not be affected if any other equipment develops a short circuit across the power line. * CAT 5/6 NETWORK CABLE NOTES: • For outdoor distances exceeding 140 feet (42.7 m), a UL497 compliant primary surge protector MUST be installed at the CAPXS. • Distances exceeding 328 feet (100 m) may be accommodated with additional hardware (available through third-party sources). 8

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

8
Wire Specifications
Use this chart to pull wires in preparation of your installation. Check the national and local building codes
BEFORE
installation.
DESCRIPTION OF WIRE RUN
WIRE SPECIFICATION
MAXIMUM RUN DISTANCE
Power Wire, secondary DC output
2-Conductor 14 AWG
2-Conductor 16 AWG
2-Conductor 18 AWG
Up to 300 feet (91.4 m)
Up to 200 feet (60.9 m)
Up to 100 feet (30.4 m)
Local Area Network (LAN)
CAT 5e or better Network Cable.
8-Conductor, 24 AWG Twisted pair
328 feet* (100 m)
Door Strike
2-Conductor 18-22 AWG Shielded
100 - 250 feet (30.5 - 76.2 m)
Magnetic Lock
2-Conductor 18-22 AWG
50 - 125 feet (15.2 - 38.1 m)
Dry Contact Closure (Most Gate Operators)
2-Conductor 18-24 AWG Shielded
500 - 2500 feet (152.4 - 762 m)
Exit Request (REX)
2-Conductor 18-24 AWG
500 feet (152.4 m)
Supervised Input
2-Conductor 18-24 AWG
500 feet (152.4 m)
Wiegand/Proximity Readers
3-Conductor 18-22 AWG Shielded
500 feet (152.4 m)
NOTE:
Main power supply and control wiring MUST be run in separate conduits. Conduits must be UL approved for low and high
voltage. Refer to the NEC for additional wiring requirements.
Category 5e cabling is the minimum performance category recommended.
Wiring shall be in accordance with the National Electrical Code (ANSI/NFPA 70), local codes and authorities having jurisdiction.
Always provide power from a dedicated source. Plug provided transformer into an outlet wired to its own 10 Amp minimum circuit
breaker. This will prevent two problems:
Other equipment cannot introduce spikes, noise, surges or dips into the power circuit that will affect the system.
The system’s operation will not be affected if any other equipment develops a short circuit across the power line.
* CAT 5/6 NETWORK CABLE NOTES:
For outdoor distances exceeding 140 feet (42.7 m), a UL497 compliant primary surge protector MUST be installed at the CAPXS.
Distances exceeding 328 feet (100 m) may be accommodated with additional hardware (available through third-party sources).