- Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 1
ENGLISH 5P 1500 RT 5P 2200 RT 5P 2200 5P 3000 RT 5P 3000 Installation and user manual Copyright © 2012 EATON All rights reserved. Service and support: Call your local service representative 614-03898-00_EN - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 2
Page 2 614-03898-00_EN - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 3
. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 4
are present within the system. It should be opened exclusively by qualified service personnel. pp The system must be properly grounded. pp The battery circuit). Product Safety pp The UPS connection instructions and operation described in the manual must be followed in the indicated order. pp - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 5
19 4.4 Operation on Battery Power 19 4.5 Return of AC Input Power 20 4.6 UPS remote control functions 20 5. Maintenance 21 5.1 Troubleshooting...21 5.2 Battery-module replacement 22 5.3 Maintenance on a UPS equipped with the HotSwap MBP module 23 6. Appendices 24 6.1 Technical specifications - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 6
5P, please read the booklet presenting the safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products of life EATON will process products at the end of their service life in compliance with local regulations. EATON works with companies in charge of - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 7
ENGLISH 2.1 Standard installations Tower installation D 2. Presentation W H Rack installation D Description 5P 1500 RT 5P 2200 RT 5P 2200 5P 3000 RT 5P 3000 H W Weights (lb/kg) 58.60 / 26.60 60.20 / 27.30 81.10 / 36.80 Dimensions (inch/mm) D xW x H 20.6 x 17.4 x 3.4 / 522 x 441.2 x 86.2 25 - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 8
2. Presentation 2.2 Rear panels 5P 1500 5P 2200 5P 3000 11 8a 1 USB communication port 2 RS232 communication port 3 Not used, connector for automatic recognition of an additional battery module 4 Slot for optional communication card 5 Connector for ROO (remote ON/OFF) or RPO (Remote - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 9
Green The UPS is operating normally. On Yellow On Red The UPS is on battery mode. The UPS has an active alarm or fault. See troubleshooting on page 21 for additional information. 614-03898-00_EN Page 9 - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 10
Efficiency and load group information The following table describes the status information provided by the UPS Note: If other indicator appears, see troubleshooting on page 21 for additional information. Operation status Standby mode Possible cause Action The UPS is OFF, waiting for start-up - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 11
user settings for load segments. Start battery test Starts a manual battery test Reset fault state Clears active fault (UPS restart notices and alarms, UPS fault, Event Log data and settings are in all supported languages. Authorizes to modify LCD screen brightness and contrast to be adapted to - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 12
2. Presentation In/Out settings ON/OFF settings Battery settings Description Load segments Auto shutdown delay Overload prealarm Cold start Forced reboot Auto restart Energy saving Sleep mode Remote command Automatic battery test Low battery warning Restart battery level Battery charge mode Deep - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 13
parts 16 RS232 communication cable 17 USB communication cable 18 Software CD-ROM 19 Manual CD-ROM 24 20 Safety instructions 21 Quick start 22 Mounting kit for 19-inch bays (RT only) 23 2 supports for the upright position 24 NMC communication card (optional) Packing materials must be disposed - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 14
3. Installation 3.2 Battery module connection Caution: Before starting the UPS, please connect the internal battery. Note: A small amount of arcing may occur when connecting the batteries. This is normal and does not damage the UPS or present any safety concern. A Connect the battery module (never - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 15
ENGLISH 3.3 Tower installation 3. Installation 3.4 Rack installation (RT only) Follow steps 1 to 4 for module mounting on the rails. 1 1 2 3 4 The rails and necessary hardware are supplied by EATON. 614-03898-00_EN 3 4 Page 15 - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 16
3. Installation 3.5 Communication ports Connection of RS232 or USB communication port (optional) The RS232 and USB communication ports cannot operate simultaneously. 1. Connect the RS232 16 or USB 17 communication cable to 17 the serial or USB port on the computer equipment. 2. Connect - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 17
the version of the FlexPDU module. 25 26 27 3.7 Connection with a HotSwap MBP module (optional) The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads (HotSwap function). 1. Connect the input socket 34 on 5P the HotSwap MBP module - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 18
3. Installation HotSwap MBP module operation ByPass UPS OUT Normal UPS ON OK to switch 29 30 31 The HotSwap MBP module has a rotary switch 31 with two positions: Normal the load is supplied by the UPS, LED 29 is on. Bypass the load is supplied directly by the AC-power source. LED 30 is on. - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 19
changes status to "UPS starting...". 5. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before continuing. See "Troubleshooting" on page 21. If the indicator is on, do not proceed until all alarms are clear. Check the UPS status from the front panel to - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 20
. pp RPO: Remote Power Off allow a remote contact to be used to disconnect all the equipment connected to the UPS. Restarting the UPS requires manual intervention. pp ROO: Remote ON/OFF allows remote action of button to shut down the UPS. These functions are obtained by opening a contact connected - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 21
. The UPS does not protect the equipment anymore. Note: The alarm message and the UPS Serial Number, then contact your service representative. Troubleshooting a UPS equipped with the HotSwap MBP module Indication Diagnostic Correction 1 The load is no longer supplied l The protected devices - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 22
-module replacement Safety recommendations The battery can cause electrocution and high short-circuit currents. The following safety precautions are required before servicing the battery components: pp remove watches, rings, bracelets and all other metal objects from the hands and arms, pp use tools - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 23
Mounting the new battery module Carry out the above instructions in reverse order. pp To ensure safety and high with the HotSwap MBP module 5P The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads (HotSwap function). Maintenance 1. - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 24
6. Appendices 6.1 Technical specifications Filter Transformer "AVR" Charger Inverter Battery Output Power @ 120 V Output Power capacity @ 120 V Output Power @ 100 V AC Input power l Rated input voltage l Input voltage range l input frequency range Output on battery power l Voltage l - Tripp Lite 5P3000 | Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 25
damage to the battery. Module with UPS outlets for installation in a bay. There are different modules with different types of outlets. UPS manual-bypass module for maintenance. There are different modules with different types of outlets. Devices or equipment connected to the UPS output. This is