Maintenance on a UPS equipped with the HotSwap MBP module

Page 23 highlights

ENGLISH 5. Maintenance Mounting the new battery module Carry out the above instructions in reverse order. pp To ensure safety and high performance, use only batteries supplied by EATON. pp Take care to firmly press together the two parts of the connector during remounting. 5.3 Maintenance on a UPS equipped with the HotSwap MBP module 5P The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads (HotSwap function). Maintenance 1. S et switch 31 to Bypass position. The red LED on the HotSwap MBP module goes ON, indicating that the load is supplied directly with AC input source power.  32 33 2. S top the UPS by pressing the button on the UPS control panel. HotSwap MBP LED 29 "UPS ON - OK to switch" goes OFF, the UPS can now be disconnected and replaced. UPS IN AC POWER ByPass UPS OUT Normal UPS ON OK to switch Return to normal operation 28 29 30 311. C heck that connected the UPS is correctly to the HotSwap MBP module. 2. Start the UPS by pressing the button on the UPS control panel. 34 LED 29 "UPS ON - OK to switch" on the HotSwap MBP module goes ON (otherwise, there is a connection error between the HotSwap MBP module and the UPS). 3. Set switch 31 to Normal position. The red LED on the HotSwap MBP module goes OFF. 614-03898-00_EN Page 23

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25

Page 23
614-03898-00_EN
ENGLISH
5. Maintenance
Mounting the new battery module
Carry out the above instructions in reverse order.
To ensure safety and high performance, use only batteries supplied by EATON.
p
Take care to firmly press together the two parts of the connector during remounting.
p
5.3 Maintenance on a UPS equipped with the HotSwap MBP module
The
HotSwap MBP
module makes it
possible to service or even replace
the UPS without affecting the connected
loads (
HotSwap
function).
Maintenance
1.
Set switch
31
to Bypass position.
The red LED on the
HotSwap MBP
module goes ON, indicating that
the load is supplied directly with
AC input source power.
2.
Stop the UPS by pressing the
button on the UPS control panel.
LED
29
"UPS ON - OK to switch"
goes OFF, the UPS can now be
disconnected and replaced.
Return to normal operation
1.
Check that the UPS is correctly
connected to the
HotSwap MBP
module.
2.
Start the UPS by pressing the
button on the UPS control panel.
LED
29
"UPS ON - OK to switch" on
the
HotSwap MBP
module goes ON
(otherwise, there is a connection error
between the
HotSwap MBP
module
and the UPS).
3.
Set switch
31
to Normal position.
The red LED on the
HotSwap MBP
module goes OFF.