Tripp Lite 5P3000 Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 21

Maintenance

Page 21 highlights

ENGLISH 5.1 Troubleshooting Operation status Batteries disconnected Overload End of battery life 5. Maintenance Possible cause The UPS does not recognize the internal batteries The batteries are disconnected Power requirements exceeds the UPS capacity (greater than 105 % of nominal) The end of the battery life is reached. Action If the condition persists, contact your service representative Verify that all batteries are properly connected. If the condition persists, contact your service representative. Remove some of the equipment from the UPS. The UPS continues to operate, but may shutdown if the load increases. The alarm resets when the condition becomes inactive. Contact your service representative for battery replacement. Event UPS fault An UPS event occurs Example: Remote Power OFF, the RPO contact has been activated to shutdown the UPS and now prevents restart. An internal failure occured with the UPS Set the contact back to its normal position and press button to restart. The UPS does not protect the equipment anymore. Note: The alarm message and the UPS Serial Number, then contact your service representative. Troubleshooting a UPS equipped with the HotSwap MBP module Indication Diagnostic Correction 1 The load is no longer supplied l The protected devices Check the wiring between when the rotary switch 33 on are connected to the UPS the UPS and the HotSwap MBP the HotSwap MBP module is set output instead of to the module (see section 3.7). to Bypass position. HotSwap MBP module. l The AC-power cord is connected to the UPS input instead of to the HotSwap MBP module. 2 The load is no longer supplied l The UPS is shut down. l Start the UPS. when the rotary switch 33 on l The wiring between the l Check the wiring between the HotSwap MBP module is set UPS and the HotSwap MBP the UPS and the HotSwap to Normal position. module is incorrect. MBP module (see section 3.7). 3 The load is no longer supplied l The rotary switch 33 on l Set the rotary switch 33 on after AC-power fails. the HotSwap MBP module the HotSwap MBP module is set to Bypass position. l The wiring between the to Normal position. l Check the wiring between UPS and the HotSwap MBP the UPS and the HotSwap module is incorrect. MBP module (see section 3.7). 614-03898-00_EN Page 21

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25

Page 21
614-03898-00_EN
ENGLISH
5. Maintenance
5.1 Troubleshooting
Operation status
Possible cause
Action
Batteries disconnected
The UPS does not recognize
the internal batteries
If the condition persists, contact
your service representative
The batteries are disconnected
Verify that all batteries are properly
connected. If the condition persists,
contact your service representative.
Overload
Power requirements exceeds the
UPS capacity (greater than 105 %
of nominal)
Remove some of the equipment
from the UPS. The UPS continues
to operate, but may shutdown if
the load increases. The alarm resets
when the condition becomes
inactive.
End of battery life
The end of the battery life is
reached.
Contact your service representative
for battery replacement.
Event
An UPS event occurs
Example:
Remote Power OFF, the RPO
contact has been activated
to shutdown the UPS and now
prevents restart.
Set the contact back to its normal
position and press
button
to restart.
UPS fault
An internal failure occured with
the UPS
The UPS does not protect
the equipment anymore.
Note:
The alarm message and
the UPS Serial Number, then contact
your service representative.
Troubleshooting a UPS equipped with the HotSwap MBP module
Indication
Diagnostic
Correction
1
The load is no longer supplied
when the rotary switch
33
on
the
HotSwap MBP
module is set
to Bypass position.
l
The protected devices
are connected to the UPS
output instead of to the
HotSwap MBP
module.
l
The AC-power cord is
connected to the UPS input
instead of to the
HotSwap
MBP
module.
Check the wiring between
the UPS and the
HotSwap MBP
module (see section 3.7).
2
The load is no longer supplied
when the rotary switch
33
on
the
HotSwap MBP
module is set
to Normal position.
l
The UPS is shut down.
l
The wiring between the
UPS and the
HotSwap MBP
module is incorrect.
l
Start the UPS.
l
Check the wiring between
the UPS and the
HotSwap
MBP
module
(see section 3.7).
3
The load is no longer supplied
after AC-power fails.
l
The rotary switch
33
on
the
HotSwap MBP
module
is set to Bypass position.
l
The wiring between the
UPS and the
HotSwap MBP
module is incorrect.
l
Set the rotary switch
33
on
the
HotSwap MBP
module
to Normal position.
l
Check the wiring between
the UPS and the
HotSwap
MBP
module
(see section 3.7).