Tripp Lite 5P3000 Eaton 5P1500RT 5P2200RT 5P2200 5P3000RT 5P3000 UPS Installat - Page 21
Maintenance
View all Tripp Lite 5P3000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 21 highlights
ENGLISH 5.1 Troubleshooting Operation status Batteries disconnected Overload End of battery life 5. Maintenance Possible cause The UPS does not recognize the internal batteries The batteries are disconnected Power requirements exceeds the UPS capacity (greater than 105 % of nominal) The end of the battery life is reached. Action If the condition persists, contact your service representative Verify that all batteries are properly connected. If the condition persists, contact your service representative. Remove some of the equipment from the UPS. The UPS continues to operate, but may shutdown if the load increases. The alarm resets when the condition becomes inactive. Contact your service representative for battery replacement. Event UPS fault An UPS event occurs Example: Remote Power OFF, the RPO contact has been activated to shutdown the UPS and now prevents restart. An internal failure occured with the UPS Set the contact back to its normal position and press button to restart. The UPS does not protect the equipment anymore. Note: The alarm message and the UPS Serial Number, then contact your service representative. Troubleshooting a UPS equipped with the HotSwap MBP module Indication Diagnostic Correction 1 The load is no longer supplied l The protected devices Check the wiring between when the rotary switch 33 on are connected to the UPS the UPS and the HotSwap MBP the HotSwap MBP module is set output instead of to the module (see section 3.7). to Bypass position. HotSwap MBP module. l The AC-power cord is connected to the UPS input instead of to the HotSwap MBP module. 2 The load is no longer supplied l The UPS is shut down. l Start the UPS. when the rotary switch 33 on l The wiring between the l Check the wiring between the HotSwap MBP module is set UPS and the HotSwap MBP the UPS and the HotSwap to Normal position. module is incorrect. MBP module (see section 3.7). 3 The load is no longer supplied l The rotary switch 33 on l Set the rotary switch 33 on after AC-power fails. the HotSwap MBP module the HotSwap MBP module is set to Bypass position. l The wiring between the to Normal position. l Check the wiring between UPS and the HotSwap MBP the UPS and the HotSwap module is incorrect. MBP module (see section 3.7). 614-03898-00_EN Page 21