Internal Battery Connection Procedure

Page 13 highlights

6 - Internal Battery Connection (continued) 1 6-2 Internal Battery Connection Procedure •1 Place the UPS system in bypass (or turn it completely off) and turn off the internal battery circuit breaker switch, located on the rear of 2 the UPS system. 3 1 4 •2 Remove the battery access bezels, located on the front of the UPS system. 5 6 2 •3 Remove the battery cartridge fuses from each fuse block. 7 8 3 •4 Disconnect the blue and white jumper cables attached to each fuse 9 block. Warning: When disconnecting the jumper cables, pull them straight away from the fuse block with even force. Do not wiggle them side-to-side, as this may damage the connector. 10 11 4 •5 Remove the fuse block bracket. Note its orientation before removal. 12 13 5 14 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60

6
1
2
3
4
5
13
6 – Internal Battery Connection
(continued)
6-2 Internal Battery Connection Procedure
Place the UPS system in bypass (or turn it completely off) and turn
off the internal battery circuit breaker switch, located on the rear of
the UPS system.
Remove the battery access bezels, located on the front of the UPS
system.
Remove the battery cartridge fuses from each fuse block.
Disconnect the blue and white jumper cables attached to each fuse
block.
Warning: When disconnecting the jumper cables, pull
them straight away from the fuse block with even force. Do not
wiggle them side-to-side, as this may damage the connector.
Remove the fuse block bracket. Note its orientation before
removal.
1
2
3
4
5