Tripp Lite SU40KX Owner's Manual for 3-Phase UPS 932688 - Page 14
potential arcing of connectors. Blown fuses must be replaced
View all Tripp Lite SU40KX manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 14 highlights
6 - Internal Battery Connection (continued) 1 6-2 Internal Battery Connection Procedure (continued) • 6 2 Slide a battery string with a red cable into an empty slot within the battery compartment. Make sure the battery string is oriented as shown in the diagram. Note: Start with the empty slots at the bottom of the battery compartment and work toward the empty slots at the top of the battery compartment. 3 TERMINALS SIDE VIEW 4 • 7 5 6 Slide a battery string with a black cable into an empty slot within the battery compartment, next to the battery string that you inserted in step 6. Make sure the battery string is oriented as shown in the diagram. Repeat steps 6 and 7 as needed until all the battery strings have been inserted into the empty battery slots. Note: Depending on the model of the UPS system, some battery compartment slots may remain empty. 6 TERMINALS SIDE VIEW 7 7 •8 Reconnect the fuse block bracket. (The letters on the fuse block bracket should be upright when it is in the correct orientation.) 8 9 8 •9 Connect the blue and white jumper cables on each internal battery 10 pack to the corresponding fuse block. The labeling next to the fuse block identifies the correct fuse block for each cable. 11 9 12 •10 Insert the battery cartridge fuses into each fuse block. The fuses are interchangeable. Make sure the fuses are firmly snapped into place. Warning: Battery cartridge fuses must be inserted last due to potential arcing of connectors. Blown fuses must be replaced 13 by a qualified electrician. Replace only with fuses of the same type and rating. 14 10 14