Tripp Lite SU40KX Owner's Manual for 3-Phase UPS 932688 - Page 32
Switching from Manual Bypass to Normal Mode Parallel UPS
View all Tripp Lite SU40KX manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 32 highlights
9 - Start-Up, Shutdown and Bypass (continued) 1 9-11 Switching from Manual Bypass to Normal Mode (Parallel UPS) 2 •1 If the UPS systems have external battery cabinets connected, switch off the external battery cabinet circuit breaker switch A of each battery pack. On the SU20KX or SU40KX, turn OFF the A battery breaker on the back of the UPS. 3 1 •2 Switch on the bypass input circuit breaker switch Q2 and the 4 output circuit breaker switch Q4 of each UPS system. Q4 5 •3 Confirm that both UPS systems are shut down, then switch off the manual bypass input circuit breaker switch Q3 of each UPS 2 system. The LCD screen will read "ON AUTO BYPASS". 6 •4 Switch on the main input circuit breaker switch Q1 of each UPS system. •5 Press the ON button A of the first UPS systems for 3 seconds (until you hear a beep), then release the button. Press the ON 7 button for the second UPS system for 3 seconds (until you hear a beep), then release the button. When the inverter of each UPS system is operating normally, they will switch to online (normal) mode at the same time. 3 Output Manual Bypass Q3 Output Manual Bypass 8 Q1 9 Output Manual Bypass Main 4 Bypass Input Input 5 10 Q2 Bypass Input Bypass Input Main Input Main Input A 11 12 13 14 32