Tripp Lite SU40KX Owner's Manual for 3-Phase UPS 932688 - Page 43
Battery Setup
View all Tripp Lite SU40KX manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 43 highlights
10 - Display and Configuration (continued) 1 10-5-2 Output Setup (continued) 5 From the "FREQ CONVERTER MODE" screen, use the scroll buttons ( , ) to select the desired setting and press the enter 2 button ( ) to confirm the setting. In frequency converter mode, the UPS will convert the incoming electrical power frequency to a different output frequency. Therefore, 60Hz can change to 50Hz output or 50Hz input can change to 60Hz output. When in frequency converter mode, bypass power is not an available 3 source (the UPS will not transfer to bypass). 4 5 5 6 Redundancy Use " " or " " to select the desired number of modules for redundancy (usually one) for redundancy, then press " " to 6 confirm. This feature allows the user to determine an acceptable power output limit to guarantee a redundancy of N+1. When this feature is enabled, the UPS will send an alarm when power usage exceeds 80% of the "non-redundant" power modules while maintaining 7 the number of redundant power modules set. For example, on an 80kVA UPS, if a Redundancy Setup is set to "1 Power Module", the UPS will trigger an alarm when you exceed 80% of 60kVA as to guarantee one power module for N+1 redundancy. 8 Press "ESC" to return to the "UPS SETUP" menu. 6 9 10-5-3 Battery Setup Use " " or " " to select "BATTERY", then press " " to confirm. 10 All parameters in this segment can only be changed when UPS is in "Bypass Mode". 11 12 13 14 43