Charger Setup, Press ESC to return to the UPS SETUP menu.

Page 46 highlights

10 - Display and Configuration (continued) 1 10-5-4 Charger Setup Use " " or " " to select "CHARGER", then press " " to confirm. 2 1 From the "CHARGER CURRENT" screen, use the scroll buttons ( , ) to select the desired setting and press the enter button ( ) to confirm the setting. Note: The default charger current setting is 7A. 3 Each internal power module has a 5 amp charger. Charger current can be set from a minimum of 2 amps total to a maximum of 5 amps per internal power module, multiplied by the number of modules. For example, the SU60KX has three internal power modules, so its charger current range is 2-15 amps. Set the 4 charger current value based on the size of the battery system. See Section 10-5-3 for more information about determining the size of the battery system. Warning: Setting the charger current too high may damage batteries and reduce their operational lifespan. Consult the 5 factory for guidance before changing the default setting. 1 2 Press " " or " " to change the charging current, then press " " to confirm. 6 Press "ESC" to return to the "UPS SETUP" menu. 7 8 9 2 10 11 12 13 14 46

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60

10
1
2
46
10-5-4 Charger Setup
Use “
” or ”
” to select “CHARGER”, then press ”
” to confirm.
From the “CHARGER CURRENT” screen, use the scroll buttons
(
,
) to select the desired setting and press the enter button
(
) to confirm the setting.
Note: The default charger current
setting is 7A.
Each internal power module has a 5 amp charger. Charger current
can be set from a minimum of 2 amps total to a maximum of 5
amps per internal power module, multiplied by the number of
modules.
For example, the SU60KX has three internal power
modules, so its charger current range is 2-15 amps.
Set the
charger current value based on the size of the battery system. See
Section 10-5-3
for more information about determining the size
of the battery system.
Warning: Setting the charger current too high may damage
batteries and reduce their operational lifespan. Consult the
factory for guidance before changing the default setting.
Press “
” or ”
” to change the charging current, then press
” to confirm.
Press “ESC” to return to the “UPS SETUP” menu.