Charger Setup, Press ESC to return to the UPS SETUP menu.
View all Tripp Lite SU40KX manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 46 highlights
10 - Display and Configuration (continued) 1 10-5-4 Charger Setup Use " " or " " to select "CHARGER", then press " " to confirm. 2 1 From the "CHARGER CURRENT" screen, use the scroll buttons ( , ) to select the desired setting and press the enter button ( ) to confirm the setting. Note: The default charger current setting is 7A. 3 Each internal power module has a 5 amp charger. Charger current can be set from a minimum of 2 amps total to a maximum of 5 amps per internal power module, multiplied by the number of modules. For example, the SU60KX has three internal power modules, so its charger current range is 2-15 amps. Set the 4 charger current value based on the size of the battery system. See Section 10-5-3 for more information about determining the size of the battery system. Warning: Setting the charger current too high may damage batteries and reduce their operational lifespan. Consult the 5 factory for guidance before changing the default setting. 1 2 Press " " or " " to change the charging current, then press " " to confirm. 6 Press "ESC" to return to the "UPS SETUP" menu. 7 8 9 2 10 11 12 13 14 46