Compaq R6000 HP Uninterruptible Power System R6000 Models User Guide - Page 19

Extended Runtime Modules, Power Distribution Units - battery

Page 19 highlights

Overview Extended Runtime Modules The UPS R6000 rear panel provides a power receptacle to which ERMs can attach. Each ERM contains battery packs in a 3U chassis. At the recommended 80 percent load, one ERM extends the available UPS runtime by up to 18 minutes. Two ERMs can be serially connected to each UPS, increasing the total available runtime by up to 30 minutes. Figure 1-7: Back panel with installed ERM Power Distribution Units Extend the capabilities of the UPS R6000 by attaching a PDU to the high current receptacle associated with load segments 1, 2, or 3. One PDU provides 12 additional receptacles to load segments to which it is attached. The High to Low Voltage Transformer (250 VA) can be connected to the UPS R6000 to supply two low-voltage outlets at 250 VA. To connect devices to the PDU, use IEC-320 jumper cords (Part No. 295633-B21). Two are provided with the PDU kit. 1-10 HP Uninterruptible Power System R6000 Models User Guide HP CONFIDENTIAL Codename: Arcuda Part Number: 347223-003 Last Saved On: 2/20/03 2:48 PM

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

Overview
1-10
HP Uninterruptible Power System R6000 Models User Guide
HP CONFIDENTIAL
Codename: Arcuda Part Number: 347223-003 Last Saved On: 2/20/03 2:48 PM
Extended Runtime Modules
The UPS R6000 rear panel provides a power receptacle to which ERMs can attach. Each
ERM contains battery packs in a 3U chassis.
At the recommended 80 percent load, one ERM extends the available UPS runtime by up to
18 minutes. Two ERMs can be serially connected to each UPS, increasing the total available
runtime by up to 30 minutes.
Figure 1-7:
Back panel with installed ERM
Power Distribution Units
Extend the capabilities of the UPS R6000 by attaching a PDU to the high current receptacle
associated with load segments 1, 2, or 3. One PDU provides 12 additional receptacles to load
segments to which it is attached.
The High to Low Voltage Transformer (250 VA) can be connected to the UPS R6000 to
supply two low-voltage outlets at 250 VA.
To connect devices to the PDU, use IEC-320 jumper cords (Part No. 295633-B21). Two are
provided with the PDU kit.