Matching the Utility Voltage, utility, battery

Page 29 highlights

LCD Configuration and Status Matching the Utility Voltage Use configuration parameters to select the UPS voltage range (see Table 3-1). • If the utility voltage is within this range, the UPS supplies utility power to the output receptacles. • If the utility voltage is outside this range, the UPS supplies battery power to the output receptacles. • If the utility voltage frequently varies outside the operating range, update the UPS configuration to match. NOTE: When you set the voltage through the LCD panel (as described in the "Set Voltage" section of this chapter), you are setting the UPS output voltage. Table 3-1: Voltage Ranges (VAC) Nominal Utility Voltage Level (VAC) 200 V Nom. ±20 208 V Nom. ±20 220 V Nom. ±20 230 V Nom. ±20 240 V Nom. ±20 Normal Utility Voltage Range 166-240 V 166-248 V 176-264 V 184-276 V 192-288 V Extended Utility Voltage Range N/A N/A N/A 166-288 V N/A To update the configuration: 1. Have a licensed electrician measure your utility voltage. 2. Use Table 3-1 to identify the operating range that most closely matches your nominal utility voltage level. 3. Update the UPS output voltage as required. Refer to the section, "Set Voltage," in this chapter for more information. 3-2 HP Uninterruptible Power System R6000 Models User Guide HP CONFIDENTIAL Codename: Arcuda Part Number: 347223-003 Last Saved On: 12/13/02 12:54 PM

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

LCD Configuration and Status
3-2
HP Uninterruptible Power System R6000 Models User Guide
HP CONFIDENTIAL
Codename: Arcuda Part Number: 347223-003 Last Saved On: 12/13/02 12:54 PM
Matching the Utility Voltage
Use configuration parameters to select the UPS voltage range (see Table 3-1).
If the utility voltage is within this range, the UPS supplies
utility
power to the output
receptacles.
If the utility voltage is outside this range, the UPS supplies
battery
power to the output
receptacles.
If the utility voltage frequently varies outside the operating range, update the UPS
configuration to match.
NOTE:
When you set the voltage through the LCD panel (as described in the “Set Voltage” section of
this chapter), you are setting the UPS
output voltage
.
Table 3-1:
Voltage Ranges (VAC)
Nominal Utility Voltage Level
(VAC)
Normal Utility Voltage Range
Extended Utility Voltage
Range
200 V Nom.
±
20
166-240 V
N/A
208 V Nom.
±
20
166-248 V
N/A
220 V Nom.
±
20
176-264 V
N/A
230 V Nom.
±
20
184-276 V
166-288 V
240 V Nom.
±
20
192-288 V
N/A
To update the configuration:
1.
Have a licensed electrician measure your utility voltage.
2.
Use Table 3-1 to identify the operating range that most closely matches your nominal
utility voltage level.
3.
Update the UPS output voltage as required. Refer to the section, “Set Voltage,” in this
chapter for more information.