Fluke 1550B FE 1550B Users Manual - Page 18
Programming a Test Voltage, V, 500 V, 1000 V, and 5000 V. Select the voltage closest
View all Fluke 1550B manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 18 highlights
1550B Users Manual Programming a Test Voltage To set a test voltage in between the pre-set test voltages proceed as follows: 1. With the Meter turned on, press the H button to select TEST VOLTAGE. V 500V 0M 00M G 0G M 00G 00k T 0 GT kM Test Voltage Display ASW05F.EPS 2. Press the V or d button to scroll through the pre-set test voltage options (250 V, 500 V, 1000 V, 2500 V, and 5000 V). Select the voltage closest to the level required. The selected test voltage appears in the upper-right of the display. 3. Press the e button. TV=xxxxV appears flashing in the lower-left of the display. 4. Press the V and d buttons to increment and decrement the voltage. When the correct voltage level shows, do not press the e button. Doing so will return the test voltage to the next lowest last pre-set voltage selection. Instead press the H button to go to the next function. Note The test voltage can be up to 10 % higher than the test voltage you select. 12