Fluke 1550B FE 1550B Users Manual - Page 29
Electrical Specifications, Live circuit warning
![]() |
View all Fluke 1550B manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 29 highlights
MegOhmMeter Specifications Electrical Specifications The meter's accuracy is specified for 1 year after calibration at operating temperatures of 0 °C to 35 °C. For operating temperatures outside the range (−20 °C to 0 °C and 35 °C to 50 °C), add ± .25 % per °C, except on the 20 % bands add ± 1 % per °C. Insulation Test Voltage (DC) Insulation Resistance Range Accuracy (+/- reading) 250 V 50 GΩ 500 V 100 GΩ 1000 V 200 GΩ 2500 V 500 GΩ 5000 V 1 TΩ Bar graph range: Insulation test voltage accuracy: Induced ac mains current rejection: unspecified 5 % 20 % unspecified unspecified 5 % 20 % unspecified unspecified 5 % 20 % unspecified unspecified 5 % 20 % unspecified unspecified 5 % 20 % unspecified 0 to 1 TΩ -0 %, +10 % at 1 mA load current 2 mA maximum Charging rate for capacitive load: 5 seconds per µF Discharge rate for capacitive load 1.5 s/µF Leakage current measurement Range 1 nA to 2 mA Accuracy +/- (5 % + 2 nA) Capacitive measurement Range 0.01 µF to 15.00 µF Accuracy +/- (15 % of reading + 0.03 µF) Timer Range 0 to 99 minutes Live circuit warning Resolution Setting: 1 minute Indication: 1 second Warning range: 30 V to 660 V ac/dc, 50/60 Hz Voltage accuracy: +/- (5 % + 2 V) 23
![](/manual_guide/products/fluke-1550b-fe-1550b-users-manual-2871470/29.png)