HP LH4r HP Netserver LT 6000r Rack Cabling Guide - Page 47

Nema 5-20p To Iec 320 C-20

Page 47 highlights

Chapter 3 Procedure for Connecting and Routing Cables to the LT 6000r Recommended 100-120 VAC Power Configuration HP NetServer LT 6000r Jumper Cables NEMA 5-15P to IEC 320 C-14 Mass Storage Unit Uninterruptible Power Supply NEMA 5-20P Detachable Cord NEMA 5-20P to IEC 320 C-20 110 VAC, 16-Amp PDU Figure 3-5. 120 VAC Configuration Figure 3-5 shows a UPS connected to the power grid through a captive cord with a NEMA 5-20P. The UPS has receptacles for use in the rack: two (on the right rear) NEMA 5-20R and six NEMA 5-15R. The PDU connects to the UPS via a detachable cord (NEMA 5-20P to an IEC 320 C20). The 120 VAC PDU has nine NEMA 5-15R and one (at the right) IEC 320 receptacle. The fan (not required if perforated doors--or no doors--are used front and back) plugs into the PDU using the right-most IEC 320 receptacle. 43

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67

Chapter 3
Procedure for Connecting and Routing Cables to the LT 6000r
43
Uninterruptible
Power Supply
NEMA 5-20P
Detachable Cord
NEMA 5-20P to IEC 320 C-20
110 VAC, 16-Amp
PDU
Jumper Cables
NEMA 5-15P
to IEC 320
C-14
Mass
Storage
Unit
HP NetServer
LT
6000r
Recommended 100-120 VAC
Power Configuration
Figure 3-5. 120 VAC Configuration
Figure 3-5 shows a UPS connected to the power grid through a captive cord with a
NEMA 5-20P. The UPS has receptacles for use in the rack: two (on the right rear)
NEMA 5-20R and six NEMA 5-15R. The PDU connects to the UPS via a
detachable cord (NEMA 5-20P to an IEC 320 C20). The 120 VAC PDU has nine
NEMA 5-15R and one (at the right) IEC 320 receptacle. The fan (not required if
perforated doors--or no doors--are used front and back) plugs into the PDU using
the right-most IEC 320 receptacle.