HP LH4r HP Netserver LT 6000r Rack Cabling Guide - Page 48

PDU Rack Power Configurations

Page 48 highlights

Chapter 3 Procedure for Connecting and Routing Cables to the LT 6000r Two 120 V PDUs per UPS Possible Two 120 VAC PDUs can be plugged into the UPS in this 120 V power configuration. There are also six NEMA 5-15R receptacles in the standard UPS which can be used for equipment in the same rack if needed. 208V PDU Rack Power Configurations The 208 VAC PDU power configurations appear as shown below in Table 3-2 and Figure 3-6. Recommended 208 VAC Power Configurations In the United States, if you are using a UPS, then use PDU model E7671A or E7672A. Attach the IEC 320 C-19 end of the E7801A cord to the PDU and attach the L6-20 end of the same cord to the NEMA L6-20 receptacle on the UPS. Alternate 208 VAC Power Configurations In the 208 VAC case, without a UPS, make sure your power system has the capacity to support the power and current needs of the components you will power. (See the section entitled "Site Preparation: Circuit Breakers.") If capacity is adequate, plug the PDU into a 208 V, L6-20 receptacle. 44

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67

Chapter 3
Procedure for Connecting and Routing Cables to the LT 6000r
44
Two 120 V PDUs per UPS Possible
Two
120 VAC PDUs can be plugged into the UPS in this 120 V power
configuration. There are also six NEMA 5-15R receptacles in the standard UPS
which can be used for equipment in the same rack if needed.
208V
PDU Rack Power Configurations
The
208 VAC PDU power configurations appear as shown below in Table
3-2
and
Figure 3-6.
Recommended 208 VAC Power Configurations
In the United States, if you are using a UPS, then use PDU model E7671A or
E7672A. Attach the IEC 320 C-19 end of the E7801A cord to the
PDU and attach
the L6-20 end of the same cord to the NEMA L6-20 receptacle on the UPS.
Alternate 208 VAC Power Configurations
In the 208 VAC case, without a UPS, make sure your power system has the
capacity to support the power and current needs of the components you will
power. (See the section entitled “Site Preparation: Circuit Breakers.") If capacity
is adequate, plug the
PDU into a 208 V, L6-20 receptacle.