7. Remove the iLO module from the chassis. To replace the component, reverse the removal procedure. Enabling the dedicated iLO management port The onboard NIC 1/shared iLO connector is set as the default system iLO port. To enable the installed dedicated iLO module: 1. During the server startup sequence after module installation, to access iLO RBSU, press the F8 key. 2. Select the Network menu. 3. Click the Network Interface Adapter field. 4. To change the setting to ON, press the spacebar. 5. To save the new settings, press the F10 key. 6. Select the File menu, and then to close iLO RBSU, click Exit. 7. To confirm exiting iLO RBSU, click OK. The server automatically reboots. IMPORTANT: If the iLO RBSU settings are reset to the default values, access to the machine will be lost. Access the physical machine, and then set the Network Interface Adapter field to ON. Non-hot-plug power supply To remove the component: 1. Power down the server (on page 27). 2. Remove all power: a. Disconnect each power cord from the power source. b. Disconnect each power cord from the server. 3. Unlock the tower bezel (on page 26). 4. Remove the access panel ("Access panel" on page 31). Removal and replacement procedures 51

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91

Removal and replacement procedures
51
7.
Remove the iLO module from the chassis.
To replace the component, reverse the removal procedure.
Enabling the dedicated iLO management port
The onboard NIC 1/shared iLO connector is set as the default system iLO port.
To enable the installed dedicated iLO module:
1.
During the server startup sequence after module installation, to access iLO RBSU, press the
F8
key.
2.
Select the
Network
menu.
3.
Click the
Network Interface Adapter
field.
4.
To change the setting to
ON
, press the spacebar.
5.
To save the new settings, press the
F10
key.
6.
Select the
File
menu, and then to close iLO RBSU, click
Exit
.
7.
To confirm exiting iLO RBSU, click
OK
. The server automatically reboots.
IMPORTANT:
If the iLO RBSU settings are reset to the default values, access to the machine will be
lost. Access the physical machine, and then set the
Network Interface Adapter
field to
ON
.
Non-hot-plug power supply
To remove the component:
1.
Power down the server (on page
27
).
2.
Remove all power:
a.
Disconnect each power cord from the power source.
b.
Disconnect each power cord from the server.
3.
Unlock the tower bezel (on page
26
).
4.
Remove the access panel ("
Access panel
" on page
31
).