HP R1500 HP R1500 G3 UPS User Guide - Page 34
Specifications, UPS physical specifications, Power protection specifications
![]() |
View all HP R1500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 34 highlights
Specifications UPS physical specifications Parameter Height Depth Width Weight Value 4.5 cm (1.75 in) 61.21 cm (24.10 in) 44.45 cm (17.5 in) 23 kg (50.5 lb) UPS input specifications NOTE: An asterisk (*) indicates the default setting. UPS model Utility voltage frequency (auto-sensing) R1500 G3 NA 50/60 Hz R1500 G3 JPN/TWN 50/60 Hz R1500 G3 INTL 50/60 Hz Available settings Branch circuit utility voltage rating (A) ("Selecting the UPS voltage configuration" on page 14) (VAC) 110, 120* 15 or 20 100*, 110 15 or 20 220, 230*, 240 16 Line cord Power cord with NEMA 5-15 plug Power cord with NEMA 5-15 plug (BSMI approved for TWN) IEC-320-C14 power inlet UPS output specifications UPS model R1500 G3 NA/JPN/TWN R1500 G3 INTL Output receptacles 4 x NEMA 5-15 4 x IEC-320-C13 Power protection specifications UPS model VA R1500 G3 NA R1500 G3 JPN/TWN 1440 1200 1320 Nominal power rating (W) 1000 900 1000 Nominal voltage setting 110, 120 100 110 Specifications 34