HP StorageWorks 2000sa HP StorageWorks P2000 G3 MSA System Event Description R - Page 28
The system transitions between 274 and 275 more than 8 times per hour.
![]() |
View all HP StorageWorks 2000sa manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 28 highlights
270 Warning Either there was a problem reading or writing the persistent IP data from the FRU ID SEEPROM, or invalid data was read from the FRU ID SEEPROM. Recommended actions • Check the IP settings (including iSCSI host channel IP settings for an iSCSI system), and update them if they are incorrect. 271 Informational The storage system could not get a valid serial number from the controller's FRU ID SEEPROM, either because it couldn't read the FRU ID data, or because the data on it isn't valid or hasn't been programmed. Therefore, the MAC address is derived by using the controller's serial number from flash. This event is only logged one time during bootup. Recommended actions • No action required. 272 Informational Expansion of the indicated snap pool has started. Recommended actions • No action required. 273 Informational PHY fault isolation has been enabled or disabled by a user for the indicated enclosure and controller module. Recommended actions • No action required. 274 Warning The indicated PHY has been disabled. Recommended actions • Look for corresponding event 275. Contact technical support if either: • Event 274 event occurs for an ingress or egress PHY and event 275 doesn't occur. • The system transitions between 274 and 275 more than 8 times per hour. 275 Informational The indicated PHY has been enabled. Recommended actions • No action required. 298 Warning The controller's real-time clock (RTC) settings might be invalid after an unexpected power loss. Recommended actions • Check the system date and time. If either is incorrect, set them to the correct date and time. • Also look for event 246 and take appropriate action. When the problem is resolved, event 299 is logged. 299 Informational The controller's real-time clock (RTC) settings were recovered after an unexpected power loss. Recommended actions • No action required. 28
![](/manual_guide/products/hewlettpackard-storageworks-2000fc-hp-storageworks-p2000-g3-msa-event-description-reference-guide-591224001-2010-df7963c/28.png)