Honeywell HM509H8908 Owners Guide - Page 14
hole and slide hose through. - installation instructions
UPC - 085267313476
View all Honeywell HM509H8908 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 14 highlights
Installation Guide Remote mount installation Cut a 1-3/4 in. diameter duct hole, install the provided 6 gasket, and slide the remote nozzle up into the duct. Secure remote nozzle to duct using #8 self-drilling Minimum 3 in. clearance sheet metal screws (4). required from nozzle outlet to duct wall. Run remote hose from 7 the humidifier to the duct nozzle location. Up to 20 ft. of hose can be used. M24770 If mounting remotely requires running hose through structural barriers (ie. wall or ceiling), cut at least a 1-3/4 in. hole and slide hose through. 8 Seal off unconditioned space with a grommet (not provided) or caulk. Attach remote hose by sliding over the nozzle 9 and adapter. Secure both hose ends with clamps (provided). IMPORTANT: Run hose continuously uphill. For horizontal runs, ensure a slope of 2 in. uphill per foot. Secure hose every horizontal foot using clamps (provided). For long horizontal runs, support the hose by first M24771 securing a length of 2 x 4 lumber, U-channel, or angle iron with the appropriate slope. Then attach the hose to the top of this support. If remote hose requires downward pitch, refer to pages 5 and 7 for instruction. 69-2036EFS-07 12