Installation and Setup Guide On-Board Triggers Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip. • If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1 cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section for transformer connections. • If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied with the control) as shown below. 8-PIN TRIGGER CONNECTOR 1 345678 8-PIN TRIGGER CONNECTOR 1 345678 KEY KEY (RED) (BLACK) (GREEN) +12 AUX. GND (-) OUTPUT 18 OUTPUT 17 (YELLOW) (PURPLE) (BLACK) (BLUE) OUTPUT 18 (GREEN) GND (-) (YELLOW) +12 AUX. (ORANGE) OUTPUT 17 (RED) COM SYNC DATA SA412OXM-1 CABLE 00-trigcon-003-V1 Figure 15a. On-Board Trigger Connector with SA4120XM-1 Cable for Use With 1361X10 Transformer 4-WIRE CABLE 00-trigcon-005-V2 Figure 15b. On-Board Trigger Connector with 4-Wire Cable for Trigger Use Only • Trigger outputs are normally high, and go low upon programmed condition. • The outputs can be programmed for inverted operation (normally low, go high) using *79 Menu mode. • Program these triggers using *80/*81 Menu modes as you would for any other relay output. • When using these outputs, note: pin 1 = output number 17 (trigger 1): 15 ohms to ground when closed (output low), open when off (output high, normal default); can be used to reset smoke detector power (must set "output normal low = yes" in *79 Menu mode, and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay module (e.g., Altronix AX-RBS) that draws less than 100mA pin 5 = output number 18 (trigger 2): 100 ohms to ground when closed (output low); open when off (output high, normal default); or can support 12V relay module that draws less than 20mA UL If on-board triggers are used, the wiring between the control unit and the UL Listed device must be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls. 2-12

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40

On-Board Triggers
Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally
located above the terminal strip.
If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1
cable (part of 4120TR Trigger Cable). See
Wiring the AC Transformer
section for
transformer connections.
If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied
with the control) as shown below.
1
3
4
5
6
7
8
SA412OXM-1
CABLE
8-PIN TRIGGER CONNECTOR
KEY
00-trigcon-003-V1
+12 AUX.
DATA
COM
SYNC
GND (-)
OUTPUT 17
(RED)
OUTPUT 18
(GREEN)
(ORANGE)
(YELLOW)
(BLUE)
(PURPLE)
(BLACK)
4-WIRE
CABLE
00-trigcon-005-V2
+12 AUX.
GND (-)
OUTPUT 17
OUTPUT 18
(RED)
(YELLOW)
(BLACK)
(GREEN)
1
3
4
5
6
7
8
8-PIN TRIGGER CONNECTOR
KEY
Figure 15a. On-Board Trigger Connector
Figure 15b. On-Board Trigger Connector
with SA4120XM-1 Cable for Use With
with 4-Wire Cable for Trigger Use Only
1361X10 Transformer
Trigger outputs are normally high, and go low upon programmed condition.
The outputs can be programmed for inverted operation (normally low, go high) using
*79 Menu mode.
Program these triggers using *80/*81 Menu modes as you would for any other relay
output.
When using these outputs, note:
pin 1 =
output number 17 (trigger 1):
15 ohms to ground when closed (output low), open when off (output high, normal
default); can be used to reset smoke detector power (must set “output normal low
= yes” in *79 Menu mode, and set for zone type 54, fire zone reset, in *80 Menu
mode); or can support 12V relay module (
e.g., Altronix AX-RBS)
that draws less
than 100mA
pin 5 =
output number 18 (trigger 2):
100 ohms to ground when closed (output low); open when off (output high,
normal default); or can support 12V relay module that draws less than 20mA
U
L
If on-board triggers are used, the wiring between the control unit and the UL Listed device must
be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.
Installation and Setup Guide