JetStream Gigabit L2 Managed Switch ■■ Requirements for Cabling Indoors When cabling indoors, keep a certain distance away from the devices that may cause highfrequency interferences, such as down-conductor cable, powerline, power transformer and electromotor. ■■ The main cable should be paved in the metal raceway of the access shaft. When cabling, keep the loop area formed by the cable itself as small as possible. ■■ Requirements for the distance between Ethernet cable and other pipelines are shown in the table. Other Pipelines Down-conductor PE Service pipe Compressed air pipe Thermal pipe (not wrapped) Thermal pipe (wrapped) Gas pipe Ethernet Cable Min Parallel Net Length L (mm) 1000 50 150 150 500 300 300 Min Parallel-overlapping Net Height H (mm) 300 20 20 20 500 300 20 The two diagrams below demonstrate parallel net length and parallel-overlapping net height. Note: The above minimum net length/height is required when metal raceway is not used. If any requirements cannot be met, you can add a steel tube or metal raceway for shielding. ■■ Requirements for the distance between Ethernet cable and high-power electric devices are in following tables. Cable 5kVA powerline Pave Way Parallel cabling One is in the grounded metal raceway or metal pipe The both are in the grounded metal raceway or metal pipe Parallel cabling One is in the grounded metal raceway or metal pipe The both are in the grounded metal raceway or metal pipe Parallel cabling One is in the grounded metal raceway or metal pipe The both are in the grounded metal raceway or metal pipe Min Parallel Length (mm) 130 70 10 300 150 80 600 300 150 12 Lightning Protection

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

JetStream Gigabit L2 Managed Switch
12
Lightning Protection
Requirements for Cabling Indoors
When cabling indoors, keep a certain distance away from the devices that may cause high-
frequency interferences, such as down-conductor cable, powerline, power transformer and
electromotor.
The main cable should be paved in the metal raceway of the access shaft. When cabling, keep the
loop area formed by the cable itself as small as possible.
Requirements for the distance between Ethernet cable and other pipelines are shown in the table.
Other Pipelines
Ethernet Cable
Min Parallel Net Length L (mm)
Min Parallel-overlapping Net
Height H (mm)
Down-conductor
1000
300
PE
50
20
Service pipe
150
20
Compressed air pipe
150
20
Thermal pipe (not
wrapped)
500
500
Thermal pipe (wrapped)
300
300
Gas pipe
300
20
The two diagrams below demonstrate parallel net length and parallel-overlapping net height.
Note:
The above minimum net length/height is required when metal raceway is not used. If any
requirements cannot be met, you can add a steel tube or metal raceway for shielding.
Requirements for the distance between Ethernet cable and high-power electric devices are in
following tables.
Cable
Pave Way
Min Parallel
Length (mm)
<2kVA powerline
Parallel cabling
130
One is in the grounded metal raceway or metal pipe
70
The both are in the grounded metal raceway or metal pipe
10
2 to 5kVA
powerline
Parallel cabling
300
One is in the grounded metal raceway or metal pipe
150
The both are in the grounded metal raceway or metal pipe
80
>5kVA powerline
Parallel cabling
600
One is in the grounded metal raceway or metal pipe
300
The both are in the grounded metal raceway or metal pipe
150