TP-Link T2600G-18TSTL-SG3216 T2600G-18TSUN V1 Instalation Guide - Page 16
Requirements for Cabling Indoors
View all TP-Link T2600G-18TSTL-SG3216 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 16 highlights
JetStream Gigabit L2 Managed Switch ■■ Requirements for Cabling Indoors When cabling indoors, keep a certain distance away from the devices that may cause highfrequency interferences, such as down-conductor cable, powerline, power transformer and electromotor. ■■ The main cable should be paved in the metal raceway of the access shaft. When cabling, keep the loop area formed by the cable itself as small as possible. ■■ Requirements for the distance between Ethernet cable and other pipelines are shown in the table. Other Pipelines Down-conductor PE Service pipe Compressed air pipe Thermal pipe (not wrapped) Thermal pipe (wrapped) Gas pipe Ethernet Cable Min Parallel Net Length L (mm) 1000 50 150 150 500 300 300 Min Parallel-overlapping Net Height H (mm) 300 20 20 20 500 300 20 The two diagrams below demonstrate parallel net length and parallel-overlapping net height. Note: The above minimum net length/height is required when metal raceway is not used. If any requirements cannot be met, you can add a steel tube or metal raceway for shielding. ■■ Requirements for the distance between Ethernet cable and high-power electric devices are in following tables. Cable 5kVA powerline Pave Way Parallel cabling One is in the grounded metal raceway or metal pipe The both are in the grounded metal raceway or metal pipe Parallel cabling One is in the grounded metal raceway or metal pipe The both are in the grounded metal raceway or metal pipe Parallel cabling One is in the grounded metal raceway or metal pipe The both are in the grounded metal raceway or metal pipe Min Parallel Length (mm) 130 70 10 300 150 80 600 300 150 12 Lightning Protection