Tripp Lite SU3000XL Owner's Manual for SmartOnline UPS 932470 - Page 5
Option 1, Option 2 - manual
View all Tripp Lite SU3000XL manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 5 highlights
Installation continued UPS Unit State when asserting EPO with AC line present: LEDs Output Fans Serial SNMP USB OFF OFF ON ON ON ON To restart the UPS unit after asserting EPO with AC line present: Option 1: 1. Verify that the EPO assertion has been removed or cleared. 2. Press OFF button until you hear a click (approx. 1 second). 3. Press ON button and UPS output will turn back on. Option 2: 1. Verify that the EPO assertion has been removed or cleared. 2. Remove AC line power to the UPS unit. 3. Reapply AC line power. Now the UPS will start back up in normal operation mode. UPS Unit State when asserting EPO without AC line power: LEDs Output Fans Serial SNMP USB OFF OFF OFF OFF OFF OFF To restart the UPS unit after asserting EPO without AC line power: 1. Verify that the EPO assertion has been removed or cleared. 2. Reapply AC line power to the UPS unit. Now the UPS will start back up in normal operation mode. 4 External Battery Connection Check to ensure that the external batteries you are connecting match the voltage listed on your UPS's battery connector. Adding external batteries will increase recharge time as well as runtime. See the battery pack owner's manual for complete installation instructions. Make sure cables are fully inserted into their connectors. Small sparks may result during battery connection; this is normal. Do not connect or disconnect battery packs when the UPS is running on battery power. Your model 4 may differ. 5 201102091 93-3092.indb 5 3/29/2011 5:36:44 PM