HP 2000sa HP StorageWorks 2312sa and 2324sa Modular Smart Array user guide (48 - Page 63

Physical requirements, Environmental requirements, Table 12 - rel

Page 63 highlights

NOTE: Connections to this device must be made with shielded cables with metallic RFI/EMI connector hoods in order to maintain compliance with FCC Rules and Regulations. Physical requirements The floor space at the installation site must be strong enough to support the combined weight of the rack, controller enclosures, expansion enclosures, and any additional equipment. The site also requires sufficient space for installation, operation, and servicing the enclosures, and also requires sufficient ventilation to allow a free flow of air to all enclosures. Table 12 and Table 13 list enclosure dimensions and weights. Weights are based on an enclosure having 12 drive modules, two controller or expansion modules, and two power supplies installed. .Table 12 Rackmount enclosure dimensions Specifications Rackmount Height Width: Depth: • Excluding cables • To back of power supply handle 3.5 inches (8.9 cm) 17.55 inches (44.58 cm) 21.3 inches (54.0 cm) 23.7 inches (60.2 cm) .Table 13 Rackmount enclosure weights Specifications 2312sa G2 Modular Smart Array • SAS drives • SATA drives 2324sa G2 Modular Smart Array • SAS drives • SATA drives MSA2000 3.5" 12-drive enclosure (12 drives) • SAS drives • SATA drives Rackmount 64.5 lb (29.3 kg) 65.5 lb (29.8 kg) 58.5 lb (26.6 kg) 54.2 lb (24.6 kg) 62 lb (28.2 kg) 63 lb (28.6 kg) Environmental requirements Table 14 Operating environmental specifications Specification Altitude Relative humidity Temperature Shock Vibration Range To 9842 feet (3000 meters), derate 35.6ºF (2ºC) for every 3281 feet (1 km) up to 9842 feet (3000 meters) 10% to 90% RH, 104ºF (40ºC) non condensing 41ºF to 104ºF (5ºC to 40ºC) 5.0 g, 10 ms, half-sine 0.5 g, 1 octave/minute, 5 Hz to 500 Hz to 5 Hz, swept-sine HP StorageWorks 2000sa G2 Modular Smart Array User Guide 63

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76

HP StorageWorks 2000sa G2 Modular Smart Array User Guide
63
NOTE:
Connections to this device must be made with shielded cables with metallic RFI/EMI connector
hoods in order to maintain compliance with FCC Rules and Regulations.
Physical requirements
The floor space at the installation site must be strong enough to support the combined weight of the rack,
controller enclosures, expansion enclosures, and any additional equipment. The site also requires sufficient
space for installation, operation, and servicing the enclosures, and also requires sufficient ventilation to
allow a free flow of air to all enclosures.
Table 12
and
Table 13
list enclosure dimensions and weights. Weights are based on an enclosure having
12 drive modules, two controller or expansion modules, and two power supplies installed.
.
.
Environmental requirements
Table 12
Rackmount enclosure dimensions
Specifications
Rackmount
Height
3.5 inches (8.9 cm)
Width:
17.55 inches (44.58 cm)
Depth:
Excluding cables
To
back of power supply handle
21.3 inches (54.0 cm)
23.7 inches (60.2 cm)
Table 13
Rackmount enclosure weights
Specifications
Rackmount
2312sa G2 Modular Smart Array
SAS drives
SATA drives
64.5 lb (29.3 kg)
65.5 lb (29.8 kg)
2324sa G2 Modular Smart Array
SAS drives
SATA drives
58.5 lb (26.6 kg)
54.2 lb (24.6 kg)
MSA2000 3.5" 12-drive enclosure
(12 drives)
SAS drives
SATA drives
62 lb (28.2 kg)
63 lb (28.6 kg)
Table 14
Operating environmental specifications
Specification
Range
Altitude
To 9842 feet (3000 meters), derate 35.6ºF (2ºC)
for every 3281 feet (1 km) up to 9842 feet (3000
meters)
Relative humidity
10% to 90% RH, 104ºF (40ºC) non condensing
Temperature
41ºF to 104ºF (5ºC to 40ºC)
Shock
5.0 g, 10 ms, half-sine
Vibration
0.5 g, 1 octave/minute, 5 Hz to 500 Hz to 5
Hz, swept-sine