HP Integrity Superdome 2 8/16 HP Integrity Superdome 2 Onboard Administrator U - Page 52
Management screen. The power modes are explained in the following table.
View all HP Integrity Superdome 2 8/16 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 52 highlights
The Superdome 2 enclosure power management system enables you to customize the configuration of the enclosure. You can select from the various modes on the Onboard Administrator Power Management screen. The power modes are explained in the following table. Mode Redundant Insight Display name Redundant AC Redundant AC Redundant Description For dc power supplies only. In this configuration, N upper and N lower power supplies are used to provide power and N upper and N lower power supplies are used to provide redundancy (where N can equal 1, 2, or 3). Up to three upper and three lower power supplies can fail without causing the enclosure to fail. When correctly wired with redundant dc line feeds, this configuration also ensures that a dc line feed failure does not cause the enclosure to power off. For ac power supplies only. In this configuration, N upper and N lower power supplies are used to provide power and N upper and N lower power supplies are used to provide redundancy (where N can equal 1, 2, or 3). Up to three upper and three lower power supplies can fail without causing the enclosure to fail. When correctly wired with redundant ac line feeds, this configuration also ensures 52 First Time Setup Wizard