LiftMaster HDSW24UL Installation Manual - English - Page 61

Swing and Slide Gate Operator UL 325 and, ASTM F2200 Site Planning Safety Checklist, Gate Safety Check

Page 61 highlights

Swing and Slide Gate Operator UL 325 and ASTM F2200 Site Planning Safety Checklist Please Print Name: Address: City/State/ZIP: Phone: Email: Satisfactory Needs Repair/Replacement Gate Safety Check - Simple steps to quickly determine if an End User's gate operator is safe. UL 325 Standard Component: Result (Circle) 1. Gate Operator is approved to current UL 325 standards (check operator label) Pass / Fail 2. Proper gate warning signs attached to both sides of gate area Pass / Fail 3. All entrapment zones protected by 2 safety devices/obstruction tested Close Side (circle two) Photo Eye Reversing Edge Inherent Reverse Pass / Fail Open Side (circle two) Photo Eye Reversing Edge Inherent Reverse Pass / Fail Other Entrapment Zones Pass / Fail *AESntrTapMmeFn2t Z2o0ne0: TShetaloncadtiaonrdwshere a person can be caught or held in a position that increases the risk of injury Gate Construction Evaluation: Gate Constructed with Safety in mind. ASTM F2200 Standards are followed Component: Result (Circle) All Gates Gates have smooth bottom edges, no protrusions exceed 1/2" beyond base of gate Pass / Fail All access controls at least 6 ft. from gate Pass / Fail Barbed tape (razor wire) at least 8 ft. above grade Pass / Fail Barbed wire at least 6 ft. above grade Pass / Fail Separate pedestrian gate - out of reach of a moving gate - vehicular gate is for automotive traffic only Pass / Fail Gate does not move on its own if disconnected from operator Pass / Fail Gates prevented from falling over if disconnected from supporting hardware Pass / Fail SWING Distance from pivot point to column edge is less than 4 in. or external entrapment protection is provided Pass / Fail Distance from open gate to wall, column, or other fixed object is greater than 16 in. or external entrapment protection is provided Pass / Fail SLIDE Roller covers on weight bearing exposed rollers 8 ft., or less, above grade Pass / Fail Meshing installed up to 6 ft. above grade if pickets spaced equal to or greater than 2 1/4 in. apart Pass / Fail Gap between gate and fence post less than 2 1/4 in. & gap protected with safety device Pass / Fail Positive stops at both fully open and fully closed positions Pass / Fail Receiver guides recessed behind receiver post for receiver guides less than 8 ft. Pass / Fail Other: Pass / Fail Comments: Comments: Figures (On Back) 1,4 1,4 Figures (On Back) 5 1,4 1,4 4 4 1 3 2 1 Please Print First & Last Name of Dealer: First & Last Name of Installer: Name of Dealership: Phone: Dealership Address (Street Address/City/State/Zip): Dealer Signature: Installer Signature: Customer Signature: © 2019 LiftMaster All Rights Reserved 300 Windsor Drive, Oak Brook, IL 60523 LMSPCLSWSL 12/19

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

Swing and Slide Gate Operator UL 325 and
ASTM F2200 Site Planning Safety Checklist
Name:
Address:
City/State/ZIP:
Phone:
Email:
Please Print
ASTM F2200 Standards
Gate Construction Evaluation:
Gate Constructed with Safety in mind. ASTM F2200 Standards are followed
Component:
Result
(Circle)
Comments:
Figures (On Back)
All Gates
Gates have smooth bottom edges, no protrusions exceed 1/2” beyond base of gate
Pass
/
Fail
5
All access controls at least 6 ft. from gate
Pass
/
Fail
1,4
Barbed tape (razor wire) at least 8 ft. above grade
Pass
/
Fail
Barbed wire at least 6 ft. above grade
Pass
/
Fail
Separate pedestrian gate – out of reach of a moving gate – vehicular gate is
for automotive traffic only
Pass
/
Fail
1,4
Gate does not move on its own if disconnected from operator
Pass
/
Fail
Gates prevented from falling over if disconnected from supporting hardware
Pass
/
Fail
SWING
Distance from pivot point to column edge is less than 4 in. or external
entrapment protection is provided
Pass
/
Fail
4
Distance from open gate to wall, column, or other fixed object is greater than
16 in. or external entrapment protection is provided
Pass
/
Fail
4
SLIDE
Roller covers on weight bearing exposed rollers 8 ft., or less, above grade
Pass
/
Fail
1
Meshing installed up to 6 ft. above grade if pickets spaced equal to or
greater than 2 1/4 in. apart
Pass
/
Fail
3
Gap between gate and fence post less than 2 1/4 in. & gap protected with safety device
Pass
/
Fail
2
Positive stops at both fully open and fully closed positions
Pass
/
Fail
1
Receiver guides recessed behind receiver post for receiver guides less than 8 ft.
Pass
/
Fail
Other:
Pass
/
Fail
© 2019 LiftMaster All Rights Reserved
300 Windsor Drive, Oak Brook, IL 60523
LMSPCLSWSL
12/19
Please Print
First & Last Name of Dealer:
Name of Dealership:
Dealership Address
(Street Address/City/State/Zip)
:
Dealer Signature:
Customer Signature:
First & Last Name of Installer:
Phone:
Installer Signature:
Satisfactory
Needs Repair/Replacement
Gate Safety Check
Simple steps to quickly determine if an End User’s gate operator is safe.
UL 325 Standard
Component:
Result
(Circle)
Comments:
Figures (On Back)
1.
Gate Operator is approved to current UL 325 standards
(check operator label)
Pass
/
Fail
2. Proper gate warning signs attached to both sides of gate area
Pass
/
Fail
1,4
3.
All entrapment zones protected by 2 safety devices/obstruction tested
1,4
Close Side
(circle two)
Photo Eye
Reversing Edge
Inherent Reverse
Pass
/
Fail
Open Side
(circle two)
Photo Eye
Reversing Edge
Inherent Reverse
Pass
/
Fail
Other Entrapment Zones
Pass
/
Fail
*Entrapment Zone: The location where a person can be caught or held in a position that increases the risk of injury