Fluke 1735 User Manual - Page 38

Split Phase

Page 38 highlights

1735 Users Manual Split Phase For Split Phase, the Neutral is center-tapped and there are two hot legs which correspond to A and B test Leads. AB is the voltage from phase to phase, which is twice that of each individual hot leg. Refer to Figure 7 and connect the leads as follows: Voltage: Network Test Leads Line 1 Line 2 Line 1 N A (L1) B (L2) C (L3) N Current: Network A (L1) B (L2) Line 1 Not connected Neutral N A (L1) B (L2) C(L3) N Test Leads 28

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82

1735
Users Manual
28
Split Phase
For Split Phase, the Neutral is center-tapped and there are two hot legs which
correspond to A and B test Leads. AB is the voltage from phase to phase,
which is twice that of each individual hot leg. Refer to Figure 7 and connect
the leads as follows:
Voltage:
Network
Test Leads
Line 1
A (L1)
Line 2
B (L2)
Line 1
C (L3)
N
N
Current:
Network
Test Leads
A (L1)
A (L1)
B (L2) Line 1
B (L2)
Not connected Neutral
C(L3)
N
N