Fluke 1735 User Manual - Page 47
Three-Phase Power Theory, the values displayed at the moment freeze and
View all Fluke 1735 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 47 highlights
Power Logger Measuring Functions - kW, kVA and kWh - kW, kVA and kVARh On pressing 21 the accumulated energy function becomes active, this must be acknowledged by pressing RUN to activate the accumulation timer. edx027.bmp The accumulation time is indicated at the top of the measurement display. A further press of 21 gives a detail view of the individual phase values. Capacitor or inductance symbols issue information about capacitive or inductive reactive power. With Hold/Run the values displayed at the moment "freeze" and the measurement is stopped or started again. Note In the individual representation of A or B or C, the active and reactive energy cannot be selected. Three-Phase Power Theory By switching the Power Network setting from wye to delta, the voltages and currents I L1, I L3, I L2 are calculated, measured and displayed. When calculating the power, selecting the delta connection will use the twowattmeter method (Blondel or Aron) measuring circuit for the calculation. 37