Fluke 1735 User Manual - Page 47

Three-Phase Power Theory, the values displayed at the moment freeze and

Page 47 highlights

Power Logger Measuring Functions - kW, kVA and kWh - kW, kVA and kVARh On pressing 21 the accumulated energy function becomes active, this must be acknowledged by pressing RUN to activate the accumulation timer. edx027.bmp The accumulation time is indicated at the top of the measurement display. A further press of 21 gives a detail view of the individual phase values. Capacitor or inductance symbols issue information about capacitive or inductive reactive power. With Hold/Run the values displayed at the moment "freeze" and the measurement is stopped or started again. Note In the individual representation of A or B or C, the active and reactive energy cannot be selected. Three-Phase Power Theory By switching the Power Network setting from wye to delta, the voltages and currents I L1, I L3, I L2 are calculated, measured and displayed. When calculating the power, selecting the delta connection will use the twowattmeter method (Blondel or Aron) measuring circuit for the calculation. 37

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82

Power Logger
Measuring Functions
37
-
kW, kVA and kWh
-
kW, kVA and kVARh
On pressing
21
the accumulated energy function becomes active, this must
be acknowledged by pressing
RUN
to activate the accumulation timer.
edx027.bmp
The accumulation time is indicated at the top of the measurement display.
A further press of
21
gives a detail view of the individual phase values.
Capacitor or inductance symbols issue information about capacitive or
inductive reactive power.
With
Hold/Run
the values displayed at the moment “freeze” and the
measurement is stopped or started again.
Note
In the individual representation of A or B or C, the active and
reactive energy cannot be selected.
Three-Phase Power Theory
By switching the Power Network setting from wye to delta, the voltages and
currents I
L1
, I
L3
, I
L2
are calculated, measured and displayed.
When calculating the power, selecting the delta connection will use the two-
wattmeter method (Blondel or Aron) measuring circuit for the calculation.