Input Power For stand alone operation: W3AQR15, W3AQR9, W3AQR3 - Refer to the wiring label on the AquaRite as well as the diagram below to determine correct wiring connections. The AquaRite is shipped from the factory with the configuration jumpers in 240VAC position. If using 120VAC, move the jumpers as shown below. For Canadian models, the AquaRite shall be connected to a circuit protected by a class A ground fault interrupter. Be sure to connect the ground wire to the green ground screw terminal located on the bottom of the enclosure. TYPICAL 240 VAC WIRING 120 VAC SUBPANEL GFCB AQUA RITE GND AQUA RITE GND GROUND PUMP PCB BONDING LUG BONDING LOOP PCB BONDING LUG IMPORTANT: MOVE JUMPERS TO POSITIONS SHOWN Bonding: Two bonding lugs are provided on the exterior enclosure, one to be used for US installations and both for Canadian. To reduce the risk of electric shock, connect the local common bonding grid in the area of the swimming pool, spa, or hot tub to these terminals with an insulated or bare copper conductor not smaller than 8 AWG US / 6 AWG Canada. Flow Switch Connector Cutout for cell cable Bonding lugs to pool bonding system 13 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40

Input Power For stand alone operation:
W3AQR15, W3AQR9, W3AQR3
- Refer to the wiring label on the AquaRite as well as the diagram
below to determine correct wiring connections.
The AquaRite is shipped from the factory with the
configuration jumpers in 240VAC position.
If using 120VAC, move the jumpers as shown below.
For
Canadian models, the AquaRite shall be connected to a circuit protected by a class A ground fault
interrupter.
Be sure to connect the ground wire to the green ground screw terminal located on the
bottom of the enclosure.
Bonding:
Two bonding lugs are provided on the exterior enclosure, one to be used for US installations
and both for Canadian. To reduce the risk of electric shock, connect the local common bonding grid
in the area of the swimming pool, spa, or hot tub to these terminals with an insulated or bare copper
conductor not smaller than 8 AWG US / 6 AWG Canada.
AQUA
RITE
AQUA
RITE
SUBPANEL
GFCB
PCB
PCB
BONDING
LUG
BONDING
LUG
BONDING
LOOP
PUMP
GROUND
GND
GND
IMPORTANT:
MOVE JUMPERS
TO POSITIONS SHOWN
TYPICAL 240 VAC WIRING
120 VAC
Bonding lugs to
pool bonding system
Cutout for
cell cable
Flow Switch
Connector
13