External Relay Speed Control Wiring Optional, for remote selection of pump speed

Page 16 highlights

DIP SWITCH STATUS PUMP ADDRESS #1 #2 #3 #4 #5 Pool Filter OFF OFF OFF OFF OFF Aux 1 / Spa Filter OFF ON OFF OFF OFF Aux 2 OFF OFF ON OFF OFF Aux 3 OFF ON ON OFF OFF Aux 4 OFF OFF OFF ON OFF Aux 5 OFF ON OFF ON OFF Aux 6 OFF OFF ON ON OFF Aux 7 OFF ON ON ON OFF Aux 8 OFF OFF OFF OFF ON Aux 9 OFF ON OFF OFF ON Aux 10 OFF OFF ON OFF ON Aux 11 OFF ON ON OFF ON Aux 12 OFF OFF OFF ON ON Aux 13 OFF ON OFF ON ON Aux 14 OFF OFF ON ON ON Lights Button OFF ON ON ON ON 5.3. External Relay Speed Control Wiring (Optional, for remote selection of pump speed) Note: For third party controls and Hayward controls that are NOT software compatible. Figure 5.3-1 Connection wire must be rated for a minimum of 300V. Inputs are rated to accept a low voltage supply of 18-30 VAC, 9-30 VDC, 50/60 Hz. The "+12V" and "COM" terminals may be used as a low voltage supply, however, these terminals also supply power to the user interface, so care must be taken when connecting to these terminals to ensure proper operation of the user interface. DIP switch #1 must be "ON". Page 16 of 36 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS 2.70 THP VS Pump Family IS3206VSP3 Rev-B

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Page 16 of 36
2.70 THP VS Pump Family
IS3206VSP3
Rev-B
DIP SWITCH STATUS
PUMP ADDRESS
#1
#2
#3
#4
#5
Pool Filter
OFF
OFF
OFF
OFF
OFF
Aux 1 / Spa Filter
OFF
ON
OFF
OFF
OFF
Aux 2
OFF
OFF
ON
OFF
OFF
Aux 3
OFF
ON
ON
OFF
OFF
Aux 4
OFF
OFF
OFF
ON
OFF
Aux 5
OFF
ON
OFF
ON
OFF
Aux 6
OFF
OFF
ON
ON
OFF
Aux 7
OFF
ON
ON
ON
OFF
Aux 8
OFF
OFF
OFF
OFF
ON
Aux 9
OFF
ON
OFF
OFF
ON
Aux 10
OFF
OFF
ON
OFF
ON
Aux 11
OFF
ON
ON
OFF
ON
Aux 12
OFF
OFF
OFF
ON
ON
Aux 13
OFF
ON
OFF
ON
ON
Aux 14
OFF
OFF
ON
ON
ON
Lights Button
OFF
ON
ON
ON
ON
5.3.
External Relay Speed Control Wiring (Optional, for remote selection of pump speed)
Note:
For third party controls and Hayward controls that are NOT software compatible.
Figure 5.3-1
Connection wire must be rated for a minimum of 300V.
Inputs are rated to accept a low voltage supply of 18-30 VAC,
9-30 VDC, 50/60 Hz. The “+12V” and “COM” terminals may be used as a low voltage supply, however,
these
terminals also supply power to the user interface, so care must be taken when connecting to these terminals to
ensure proper operation of the user interface. DIP switch #1 must be “ON”.