HP D2200sb HP StorageWorks D2200sb PCIe Storage Blade Maintenance and Service - Page 44
Specifications, Environmental specifications, Storage blade specifications
View all HP D2200sb manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 44 highlights
Specifications Environmental specifications Specification Value Temperature range* Operating Storage Relative humidity** Operating Storage 10°C to 35°C (50°F to 95°F) Maximum rate of change is 10º C/hr (50º F/hr) -30°C to 60°C (-22°F to 140°F) Maximum rate of change is 20º C/hr (68º F/hr) 20% to 80% relative humidity (Rh), 28º C (82.4º F) maximum wet bulb temperature, non-condensing 5% to 90% relative humidity (Rh), 38.7º C (101.66º F) maximum wet bulb temperature, non-condensing Altitude † Operating Non-operating 3048 m (10,000 ft) This value may be limited by the type and number of options installed. 9144 m (30, 000 ft) * Temperature ratings shown are for sea level. An altitude derating of 1°C per 300 m (1.8°F per 1,000 ft) to 3048 m (10,000 ft) is applicable. No direct sunlight is allowed. The upper limit may be limited by the type and number of options installed. ** Storage maximum humidity of 90% is based on a maximum temperature of 45°C (113°F). Altitude maximum for storage corresponds to a pressure minimum of 70 KPa. † Maximum allowable altitude change rate is 457 m/min (1500 ft/min). Storage blade specifications Specification Height Depth Width Weight (maximum) Weight (no drives installed) Value 5.56 cm (2.19 in) 50.95 cm (20.06 in) 18.16 cm (7.15 in) 5.0 kg (11.0 lb) 3.6 kg (8.0 lb) Specifications 44