HP LH4r HP Netserver LXr 8500 Rack Cabling Guide - Page 42

Component, Model, Power, Current

Page 42 highlights

Chapter 3 Procedure for Connecting and Routing Cables to the LXr 8500 Table 3-2. 230/240 VAC PDU Power and Current Component1 Model Power Power Current (VA) (W) (A)2 208 VAC PDU E7671A or E7672A N/A N/A max 16 HP NetServer D7057A, 500 MHz, 512K Cache 1121 1077 4.9 LXr 85003 D7133A, 500 MHz, 1MB Cache D7058A, 500 MHz, 2MB Cache HP NetServer Rack Storage/12 is D5989A 547 538 2.3 Mass Storage Rack Storage/12FC is D5991A Unit HP Console Switch J1497B 42 29 0.2 Note 1 More ratings are listed in Table 2-6. For a full list of power ratings, see the rack configuration utilities (for instance, Rack Assistant) on the HP Web Site. Note 2 Indicated current ratings are for use in selecting PDU and UPS components and may not reflect actual measured amounts. Note 3 When ordered through select express, the D7057A becomes D7062AV, the D7133A becomes D7063AV, and the D7058A becomes D7134AV. Description of the Recommended 230/240 VAC Configuration Figure 3-6 shows a UPS connected to the power mains through an attached power cord (appropriate cords are supplied for each country). The UPS has eight IEC 320 receptacles for use with the rack jumper cords. The E7671A PDU connects to the UPS via a detachable line cord, which connects to the PDU via a C-19 plug. This cord connects to the UPS with a C-20 plug. The 200/240 VAC PDU has two IEC 320, C-19 and six IEC 320, C-13 receptacles for connecting rack jumper cords. 38

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59

Chapter 3
Procedure for Connecting and Routing Cables to the LXr 8500
38
Table 3-2. 230/240 VAC PDU Power and Current
Component
1
Model
Power
(VA)
Power
(W)
Current
(A)
2
208 VAC
PDU
E7671A or E7672A
N/A
N/A
max 16
HP NetServer
LXr 8500
3
D7057A, 500 MHz, 512K Cache
D7133A, 500 MHz, 1MB Cache
D7058A, 500 MHz, 2MB Cache
1121
1077
4.9
HP NetServer
Mass Storage
Unit
Rack Storage/12 is D5989A
Rack Storage/12FC is D5991A
547
538
2.3
HP Console
Switch
J1497B
42
29
0.2
Note 1
More ratings are listed in Table 2-6. For a full list of power ratings, see the rack
configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 2
Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Note 3
When ordered through select express, the D7057A becomes D7062AV, the
D7133A becomes D7063AV, and the D7058A becomes D7134AV.
Description of the Recommended 230/240 VAC Configuration
Figure
3-6
shows a UPS connected to the power mains through an attached power
cord (appropriate cords are supplied for each country). The UPS has eight IEC
320 receptacles for use with the rack jumper cords. The E7671A
PDU connects to
the UPS via a detachable line cord, which connects to the PDU via a C-19 plug.
This cord connects to the UPS with a C-20 plug. The 200/240 VAC
PDU has two
IEC 320, C-19 and six IEC 320, C-13 receptacles for connecting rack jumper
cords.