HP LH4r HP Netserver Service Handbook, Volume 3 - High-End - Page 53
Cooling Specifications
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 53 highlights
Specifications Video Expansion Slots Dimensions System dimensions Rack space System weight Cooling Specifications Maximum heat output Operating temperature Operating humidity Power Specifications Voltage and frequency Maximum continuous power input Maximum inrush current Delayed action circuit breaker recommended Power availability Integrated 1024x768sx256 60-75hz Video, 1 meg video RAM (Cirrus 5446) Total PCI Buses:3, Total I/O slots:10 •4 64-bit PCI Full Length on PCI 2 (Hot Swap) •5 32-bit PCI Full Length on PCI 1 •1 shared 32-bit PCI/ISA Full Length on PCI 0 12.25 in. high x 17.5 in. wide x 28 in. deep (31.1 cm high x 44.5 cm wide x nn 71.1 deep) 7 EIA units 130 lb. (59 kg) 3675 BTU/hour 41 to 95 degrees F (5 to 35 degrees C) 20% to 80% Rh 200-240 VAC; 50/60 Hz 1100 W for a four-CPU configuration; 5.6 A at 200/208 V, 4.9 A at 230/240 V. 150 A for 4 ms North America: a 20 A minimum circuit is to be used with one NEMA AB1 class 14B breaker for each 16 A power distribution unit (PDU) that is connected to an HP NetServer LXr 8000. Europe (a single server in a rack): use a 16 A-minimum circuit with one IEC MCB C-type breaker for each 16-amp PDU. Europe (multiple servers in a rack): use a 16-amp-minimum circuit with one IEC MCB D-type breaker for each 16 A PDU. 1500 DC watts continuous NOTE Some local electrical codes do not allow a 16-amp device to be connected to a 16amp service. Consult a qualified electrician or local regulatory authority before beginning electrical site preparation. 47