Configuration 4: 200–240 V line-to-line three-phase configuration with single- phase control

Page 13 highlights

Power-cable specifications Configuration Wire Terminals External diameter range Three-phase line Single-phase line 5 wires, L1/L2/L3/N/PE 3 wires, L/N/PE Strained Cu minimum, 6 mm2 or 10 AWG Strained Cu minimum, 1.5 mm² or 16 AWG Lines, ferrule terminals, PE, M8 ring terminal Lines, ferrule terminals, PE, M4 ring terminal 22.0-33.0 mm 5.0-11.0 mm Configuration 4: 200-240 V line-to-line three-phase configuration with single- phase control Power specifications Three-phase line Single-phase control Number of power wires 4 (L1/L2/L3/PE) 3 (L/N/PE) Input voltage (line to line) 200-240 V 100-240 V Input frequency 50/60 Hz 50/60 Hz Power consumption (typical) 8-10 kW 0.5 kW Maximum load current (per phase) 48 A 10 A Branch circuit-breaker specifications Three-phase Two-phase control 3 poles, 50/60 A 2 poles, 15/16/20 A Power-cable specifications Configuration Wire Terminals External diameter range Three-phase line Single-phase line 4 wires, L1/L2/L3/PE 3 wires, L/N/PE Strained Cu minimum, 10 mm² or 6 AWG Strained Cu minimum, 2.5 mm² or 16 AWG Lines, ferrule terminals, PE, M8 ring terminal Lines, ferrule terminals, PE, M4 ring terminal 22.0-33.0 mm 5.0-11.0 mm ENWW System operation requirements 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

Power-cable specifications
Three-phase line
Single-phase line
Configuration
5 wires, L1/L2/L3/N/PE
3 wires, L/N/PE
Wire
Strained Cu minimum, 6 mm2 or 10 AWG
Strained Cu minimum, 1.5 mm² or 16 AWG
Terminals
Lines, ferrule terminals, PE, M8 ring terminal
Lines, ferrule terminals, PE, M4 ring terminal
External diameter range
22.0–33.0 mm
5.0–11.0 mm
Configuration 4: 200–240 V line-to-line three-phase configuration with single- phase control
Power specifications
Three-phase line
Single-phase control
Number of power wires
4 (L1/L2/L3/PE)
3 (L/N/PE)
Input voltage (line to line)
200–240 V
100–240 V
Input frequency
50/60 Hz
50/60 Hz
Power consumption (typical)
8–10 kW
0.5 kW
Maximum load current (per phase)
48 A
10 A
Branch circuit-breaker specifications
Three-phase
3 poles, 50/60 A
Two-phase control
2 poles, 15/16/20 A
Power-cable specifications
Three-phase line
Single-phase line
Configuration
4 wires, L1/L2/L3/PE
3 wires, L/N/PE
Wire
Strained Cu minimum, 10 mm² or 6 AWG
Strained Cu minimum, 2.5 mm² or 16 AWG
Terminals
Lines, ferrule terminals, PE, M8 ring terminal
Lines, ferrule terminals, PE, M4 ring terminal
External diameter range
22.0–33.0 mm
5.0–11.0 mm
ENWW
System operation requirements