HP Latex 800 Site Preparation Guide - Page 18
Site preparation requirements
![]() |
View all HP Latex 800 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 18 highlights
The following grounding tasks must be fulfilled to meet the site preparation requirements: ● Grounding wires must be insulated and at least equal in size to the phase conductors. ● Ground impedance must be less than 0.5 Ω or comply with the Electrical Code requirements of the local jurisdiction of the country where the equipment is installed. 14 Chapter 2 Site preparation requirements
![](/manual_guide/products/hewlettpackard-latex-700-site-preparation-guide-3f9fd1b/18.png)
The following grounding tasks must be fulfilled to meet the site preparation requirements:
●
Grounding wires must be insulated and at least equal in size to the phase conductors.
●
Ground impedance must be less than 0.5 Ω or comply with the Electrical Code requirements of the local
jurisdiction of the country where the equipment is installed.
14
Chapter 2
Site preparation requirements