HP R1500 UPS R6000 Models User Guide - Page 63
Battery Runtime, Environmental Specifications, Table C-5, Load Effect on Backup Time
![]() |
View all HP R1500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 63 highlights
Specifications Battery Runtime Table C-5: Load Effect on Backup Time Load % 100 80 50 80% plus 1 ERM 80% plus 2 ERMs Estimated Backup Time Greater than 6 minutes Greater than 8 minutes Greater than 15 minutes Greater than 18 minutes Greater than 30 minutes Environmental Specifications Table C-6: Environmental Specifications Feature Operating temperature Relative humidity Operating altitude Audible noise Specification 10oC - 40o C (50 oF -104oF) 20 - 80%; non-condensing Up to 3000 m (10,000 ft) above sea level Less than 55 dBA @ 1 meter C-4 HP Uninterruptible Power System R6000 Models User Guide
![](/manual_guide/products/hewlettpackard-rt3000-ups-r6000-models-user-guide-4874ede/63.png)
Specifications
C-4
HP Uninterruptible Power System R6000 Models User Guide
Battery Runtime
Table C-5:
Load Effect on Backup Time
Load %
Estimated Backup Time
100
Greater than 6 minutes
80
Greater than 8 minutes
50
Greater than 15 minutes
80% plus 1 ERM
Greater than 18 minutes
80% plus 2 ERMs
Greater than 30 minutes
Environmental Specifications
Table C-6:
Environmental Specifications
Feature
Specification
Operating temperature
10
o
C - 40
o
C (50
o
F -104
o
F)
Relative humidity
20 - 80%; non-condensing
Operating altitude
Up to 3000 m (10,000 ft) above sea level
Audible noise
Less than 55 dBA @ 1 meter