HP Rp7410 Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 47

Table 2-4, Typical Raised Floor Specifications Continued

Page 47 highlights

Facility Guidelines Facility Characteristics Table 2-4 Typical Raised Floor Specifications (Continued) Itema Rating Ultimate load 4000 lb (1814 kg) per panel Rolling load Average floor load 400 lb (181 kg) 500 lb (227 kg) a. From Table 2-3 on page 25 b. With 0.08 in (0.2 cm) of span maximum deflection Windows Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the cooling system. Chapter 2 27

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74

Chapter 2
Facility Guidelines
Facility Characteristics
27
Windows
Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems.
Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight
places an additional load on the cooling system.
Ultimate load
4000 lb (1814 kg) per
panel
Rolling load
400 lb (181 kg)
Average floor load
500 lb (227 kg)
a. From Table 2-3 on page 25
b.
With 0.08 in (0.2 cm) of span maximum deflection
Table 2-4
Typical Raised Floor Specifications (Continued)
Item
a
Rating