HP Rp7410 Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers - Page 63
Example Power Consumption Theoretical Maximum and Air
View all HP Rp7410 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 63 highlights
System Requirements Summary Power Consumption and Air Conditioning Table A-1 Example Power Consumption (Theoretical Maximum) and Air Conditioning Requirement Summary Component Chassis Cell Board (PA8700) PCI Card (Maximum 25W) Power Supply (BPS) DVD Disk Drive Core I/O PCI Power Supply Quantity Multiply Quantity By: Power Dissipated (kilowatts) 1 426 426.00 (.426) 2 746 1492.00 (1.492) 16 25 400.00 (.400) 2 125 250.00 (.250) 1 20 20.00 (.020) 4 25 100.00 (.100) 2 70 140.00 (.140) 2 47 94.00 (.094) Total 2922.00 (2.922) Air Conditioning Required (tons) (kilowatts/3.517 =tons) 0.121 0.424 0.114 0.071 0.006 0.028 0.040 0.027 .831 Table A-2 Power Consumption (Theoretical Maximum) and Air Conditioning Requirement Summary Component Chassis Cell Board (PA8700) PCI Card (Maximum 25W) Power Supply (BPS) DVD Disk Drive Core I/O PCI Power Supply Quantity 1 Multiply Quantity By: Power Dissipated (kilowatts) Air Conditioning Required (tons) (kilowatts/3.517 =tons) 426 746 25 125 20 25 70 47 Total 426.00 (.426) 0.121 Appendix A 43