HP StorageWorks 2/140 FW 08.01.00 McDATA Products in a SAN Environment Plannin - Page 290
Dimensions, Power Requirements, Clearances, Cabinet Footprint, Input frequency
![]() |
View all HP StorageWorks 2/140 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 290 highlights
Product Specifications Dimensions The Fabricenter cabinet has the following physical dimensions: Height: 186.1 centimeters (73.2 inches). A total of 39 rack units (39 U) are available internal to the cabinet for product installation. Width: 61.0 centimeters (24.0 inches). Depth: 105.4 centimeters (41.5 inches). Weight (no installed products): 153.2 kilograms (337.0 pounds). Weight (shipping container): 50.9 kilograms (112.0 pounds). Power Requirements The Fabricenter cabinet has the following power requirements: Input voltage: 200 to 240 VAC. Input current: 30.0 amps at 208 VAC. Input frequency: 47 to 63 Hz. Clearances The Fabricenter cabinet has the following cooling airflow and service clearances. Cooling airflow clearances: Right and left side: No clearance required. Front and rear: 15.2 centimeters (6.0 inches). Service clearances: Right and left side: No clearance required. Front and rear: 91.4 centimeters (36.0 inches). Cabinet Footprint Figure A-1 illustrates the Fabricenter cabinet footprint. The bottom denotes the front of the cabinet. The illustration includes: 1. Cabinet-leveling screws (four total). 2. Cooling airflow cutouts (eight total). 3. Fibre Channel cable cutouts (two total). 4. Caster wheel attachments (four total). 5. Power cable cutout (one). A-8 McDATA Products in a SAN Environment - Planning Manual
![](/manual_guide/products/hewlettpackard-316095b21-fw-080100-mcdata-products-san-environment-planning-guide-620000124510-2005-cc7608a/290.png)