HP Xw460c HP BladeSystem c7000 Enclosure Setup and Installation Guide - Page 66

Limit AC Input VA, Power Savings, Enabled, Disabled, OA1 IP Addr, Enclosure Name, Clear, Rack Name

Page 66 highlights

o None Limit AC Input VA-The default setting is Not Set. You can change the Max AC Watts in increments of 50 Watts. IMPORTANT: When calculating the Power Limit Watts AC value, derate the circuit to 80% of the maximum to prevent tripping the circuit breaker (United States only). IMPORTANT: If your facility cannot support the calculated peak Watts AC, set the Power Watts AC value to match the capability of your facility. Power Savings-The default setting is Enabled. The following selections are valid: o Enabled-You can place some of the power supplies on standby automatically to increase overall enclosure power subsystem efficiency. o Disabled-All power supplies share the load; the power subsystem efficiency varies based on load. OA1 IP Addr-The default setting is DHCP. If no IP address is received, the IP address is 0.0.0.0. The IP address, mask, and gateway are set within this option. OA2 IP Addr-If this module is present, the default setting is DHCP. If no IP address is received, the IP address is 0.0.0.0. If only one Onboard Administrator module is installed, the screen will display Not Present. Enclosure Name-The default setting is a unique factory-assigned name. The accepted character values are 0-9, A-Z, a-z, -, _ and . is used to signal the end of the name. NOTE: Do not use the symbol in the middle of a text field. Entries in text fields will be truncated to the last character before the symbol. TIP: Select Clear from the navigation bar to quickly clear entries in text fields up to the symbol. Rack Name-The default setting is UnnamedRack The accepted character values are 0-9, A-Z, a-z, -, _ and . is used to signal the end of the name. Insight Display PIN#-The default setting is Not Set. HP recommends that you set a PIN to protect the enclosure configuration from unauthorized changes. You must enter the PIN after each inactivity period to change options in the Enclosure Settings menu. The accepted character values are 0-9, A- Z, a-z, -, _ and . is used to signal the end of the name. HP BladeSystem Insight Display 66

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101

HP BladeSystem Insight Display
66
o
None
Limit AC Input VA—
The default setting is Not Set. You can change the Max AC Watts in increments
of 50 Watts.
IMPORTANT:
When calculating the Power Limit Watts AC value, derate the circuit to 80% of
the maximum to prevent tripping the circuit breaker (United States only).
IMPORTANT:
If your facility cannot support the calculated peak Watts AC, set the Power
Watts AC value to match the capability of your facility.
Power Savings—
The default setting is Enabled. The following selections are valid:
o
Enabled—
You can place some of the power supplies on standby automatically to increase
overall enclosure power subsystem efficiency.
o
Disabled—
All power supplies share the load; the power subsystem efficiency varies based on
load.
OA1 IP Addr—
The default setting is DHCP. If no IP address is received, the IP address is 0.0.0.0.
The IP address, mask, and gateway are set within this option.
OA2 IP Addr—
If this module is present, the default setting is DHCP. If no IP address is received, the
IP address is 0.0.0.0. If only one Onboard Administrator module is installed, the screen will display
Not Present.
Enclosure Name—
The default setting is a unique factory-assigned name. The accepted character
values are 0–9, A–Z, a–z, -, _ and
.
is used to signal the end of the name.
NOTE:
Do not use the
symbol in the middle of a text field. Entries in text fields will be
truncated to the last character before the
symbol.
TIP:
Select
Clear
from the navigation bar to quickly clear entries in text fields up to the
symbol.
Rack Name—
The default setting is UnnamedRack The accepted character values are 0–9, A–Z, a–z,
-, _ and
.
is used to signal the end of the name.
Insight Display PIN#—
The default setting is Not Set. HP recommends that you set a PIN to protect the
enclosure configuration from unauthorized changes. You must enter the PIN after each inactivity
period to change options in the Enclosure Settings menu. The accepted character values are 0–9, A–
Z, a–z, -, _ and
.
is used to signal the end of the name.