HP Xw460c HP BladeSystem c7000 Enclosure Setup and Installation Guide - Page 80

Power errors, Cooling errors, Location errors, Configuration errors, interconnect modules.

Page 80 highlights

• Previous Alert-Displays the previous alert. Power errors Power errors can occur because of insufficient power to bring up an enclosure. Power errors can occur on blades, storage blades, or interconnect modules. To correct a power error: 1. Use the arrow buttons to navigate to Fix This, and press OK. 2. Review and complete the corrective action suggested by the Insight Display. In most cases, you must either add power supplies to the enclosure or remove the indicated components. Cooling errors Cooling errors occur when too few fans are installed in the enclosure or when the existing fans are not installed in an effective configuration. Cooling errors can occur on blades, storage blades, or interconnect modules. To correct a cooling error: 1. Use the arrow buttons to navigate to Fix This, and press OK. 2. Review and complete the corrective action suggested by the Insight Display. In most cases, you must either add fans to the enclosure, correct the fan configuration, or remove the indicated components. Location errors Location (installation) errors occur when the component is not installed in the appropriate bay. Location errors can occur on blades, storage blades, power supplies, and fans. To correct a location error: 1. Use the arrow buttons to navigate to Fix This, and press OK. 2. Review and complete the corrective action suggested by the Insight Display. Remove the indicated component, and install it into the correct bay. The Insight Display will indicate the correct bay number. Configuration errors Configuration errors can occur if the interconnect modules are installed in the wrong bays or if mezzanine cards are installed in the wrong connectors in the blade. Configuration errors can occur on blades and interconnect modules. To correct a configuration error: 1. Use the arrow buttons to navigate to Fix This, and press OK. 2. Review and complete the corrective action suggested by the Insight Display. Depending on the error received, do one of the following: o Remove the indicated interconnect module and install it into the correct bay (the Insight Display indicates the correct bay). o Remove the blade to correct the mezzanine card installation (the Insight Display will indicate the correct bay). For information on installing the mezzanine card, see the server-specific user guide on the Documentation CD. Troubleshooting 80

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101

Troubleshooting 80
•
Previous Alert—Displays the previous alert.
Power errors
Power errors can occur because of insufficient power to bring up an enclosure. Power errors can occur on
blades, storage blades, or interconnect modules.
To correct a power error:
1.
Use the arrow buttons to navigate to
Fix This,
and press
OK.
2.
Review and complete the corrective action suggested by the Insight Display. In most cases, you must
either add power supplies to the enclosure or remove the indicated components.
Cooling errors
Cooling errors occur when too few fans are installed in the enclosure or when the existing fans are not
installed in an effective configuration. Cooling errors can occur on blades, storage blades, or interconnect
modules.
To correct a cooling error:
1.
Use the arrow buttons to navigate to
Fix This,
and press
OK.
2.
Review and complete the corrective action suggested by the Insight Display. In most cases, you must
either add fans to the enclosure, correct the fan configuration, or remove the indicated components.
Location errors
Location (installation) errors occur when the component is not installed in the appropriate bay. Location
errors can occur on blades, storage blades, power supplies, and fans.
To correct a location error:
1.
Use the arrow buttons to navigate to
Fix This,
and press
OK.
2.
Review and complete the corrective action suggested by the Insight Display. Remove the indicated
component, and install it into the correct bay. The Insight Display will indicate the correct bay
number.
Configuration errors
Configuration errors can occur if the interconnect modules are installed in the wrong bays or if mezzanine
cards are installed in the wrong connectors in the blade. Configuration errors can occur on blades and
interconnect modules.
To correct a configuration error:
1.
Use the arrow buttons to navigate to
Fix This,
and press
OK.
2.
Review and complete the corrective action suggested by the Insight Display. Depending on the error
received, do one of the following:
o
Remove the indicated interconnect module and install it into the correct bay (the Insight Display
indicates the correct bay).
o
Remove the blade to correct the mezzanine card installation (the Insight Display will indicate the
correct bay). For information on installing the mezzanine card, see the server-specific user guide
on the Documentation CD.